KNX control elements and application parameters
Control element: "Dimmer slider"
Product manual 2CKA001473B5342
│
130
10.4.9 Slider
sends
Options:
When releasing the slider
Cyclic
The parameter is used to specify whether the signal is sent "When releasing the slider" or
"Cyclic".
–
When releasing the slider
: No additional parameters available.
–
Cyclic
: The following supplementary parameter is available:
Telegram is repeated every [sec.]:
Options:
Setting option from 0.25 - 1.25 seconds
The parameter is used to specify the space of time between two dimming telegrams.
10.4.10 Brightness change [%]
Options:
Setting option from 1 - 20
The parameter is used to set the number of steps (in percent) for dimming. The brightness
change takes place when the slider is released.
10.4.11 Enable 1-bit communication object "Disable"
Options:
Deactivated
Activated
There is the option of temporarily disabling the function via an additional communication object
"Disable".