KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA001473B5342
│
264
10.24.101
Setpoint adjustment — Resetting the manual adjustment for change of operating
mode
Options:
Deactivated
Activated
If the device switches to a new operating mode, the manual adjustment is deleted and the
parameterised setpoint temperature for the operating mode plus any change by the base
setpoint value object will be applied if this parameter is activated. Example: Comfort
temperature of 21°C plus manual adjustment of 1.5°C = 22.5°C. Change to Eco with
programmed temperature 17°C. The device regulates the temperature to 17°C, since the
manual adjustment is deleted.
If the parameter is deactivated, the manual setpoint adjustment will be added to the temperature
in the new operating mode. Example: Comfort temperature of 21°C plus manual adjustment of
1.5°C = 22.5°C. If the system switches to Eco with a parameterised temperature of 17°C, the
device regulates the temperature to 18.5°C, since the manual adjustment is added.
10.24.102
Setpoint adjustment — Resetting the manual adjustment via object
Options:
Deactivated
Activated
If this parameter is activated, a separate object can be used to delete the manual adjustment at
any time. Example of application: Resetting the manual adjustment on all devices located in an
office building using a system clock.
10.24.103
Setpoint adjustment — Permanent storage of on-site operation
Options:
Deactivated
Activated
If this parameter is activated, the manual settings for setpoint and, where applicable, fan speed
level, as well as the value of the "Basic load" object, will be stored in the device and re-activated
after a reset. The same applies to the operating mode.
If the device is re-programmed, the stored setpoint values will also be deleted.
Содержание Busch-SmartTouch ST/A10.11-811
Страница 59: ...Commissioning via Busch free home Product manual 2CKA001473B5342 59 Abb 33 Other settings Part 2 ...
Страница 60: ...Commissioning via Busch free home Product manual 2CKA001473B5342 60 Abb 34 Other settings Part 3 ...
Страница 307: ...Operation Product manual 2CKA001473B5342 307 12 2 2 Additional basic principles Fig 46 Basic principles ...