background image

6

A

B

C

D

Zone Control

User Interface &

Smart Sensor(s)

Green

Yellow

White

Red

OAT

HUM

COM
24V

Humidifier

Connection

A

B

C

D

 

OAT

Sensor

(Optional)

A B C D

A B C D

Damper

Control

module

A B C D

Indoor

Unit

Communicating

AC or HP

A04018

Fig. 12 -- Communicating Indoor Unit w/2--Stage Puron

r

Refrigerant Communicating Outdoor Unit

A

B

C

D

Zone Control

User Interface &

Smart Sensor(s)

Green

Yellow

White

Red

OAT

HUM

COM
24V

Humidifier

Connection

OAT

Sensor

A B C D

A B C D

Damper

Control

module

A B C D

Indoor

Unit

C

Y

1-Stage AC

Y/Y2

A04019

Fig. 13 -- Connection Diagram for Furnace or FE Fan Coil

with Non--Communicating 1--Stage AC

A

B

C

D

Zone Control

User Interface &

Smart Sensor(s)

Green

Yellow

White

Red

A

B

C

D

A

B

C

D

Damper

Control

module

A

B

C

D

Variable-Speed

Fan Coil

1-Spd. HP

HUM

C

Y

W2

 Y

O

C

R

O

R

W

OAT

OAT

Sensor

Humidifier

Connection

G

A07149

Fig. 14 -- Connection Diagram for FE Fan Coil with

Non-- Communicating 1--stage HP

Humidifier Connection

A 24VAC bypass or fan powered humidifier may be installed.

NOTE

:

Do Not Use

a traditional humidistat to control humidifier

operation. If a humidifier is installed, let the Evolution Zone
Control operate humidifier.

Bypass Humidifiers

A bypass humidifier should be wired directly to the furnace or fan

coil HUM and 24VAC COM terminals. The Evolution Zone
Control will automatically energize the HUM output during a call

for humidification.

Fan Powered Humidifiers

Most fan powered humidifiers produce internal 24VAC in order to
energize upon a switch or contact closure. For this application, a

24VAC N.O. Isolation Relay (DPST)

MUST

be used to prevent

mixing the internal humidifier power with the indoor equipment
transformer. Applying 24VAC isolation relay coil to furnace or fan

coil HUM and COM terminals will allow the Evolution Zone
Control to automatically energize the HUM output during a call for

humidification. The N.O. relay contacts will be used to energize the
humidifier. See fan powered humidifier installation instructions for

more details.

EQUIPMENT HAZARD

Failure to follow this caution may result in equipment damage.
Do not apply 24VAC fan powered humidifier (with internal

power supply) direct to indoor unit HUM and COM terminals.

CAUTION

!

INITIAL POWER--UP

NOTE

:

Refer to Functional Overview (Fig. 15) to become

familiar with key function buttons such as “System On/Off”,
“Zone”, “Fan”, “Left--Side” and “Right--Side” buttons, etc. These
function buttons will be used frequently during setup.

HOLD

COOL

HEAT

SCHEDULE

VACATION

PROGRAM

SCROLL

BASIC

ADVANCED

SETUPS

Schedule

to program

temperature

schedule

Vacation

to start/end

vacation

Basic

to set time,

humidity

Advanced

for all other

settings

Scroll

up & down

Fan Button

Display Screen

(LCD)

Right-Side

Button

Heat Button

Cool Button

Temperature

(+/-) Button

System

On/Off Button
Basic & Advanced

Setup Buttons

Flip Down

Door

Left-Side

Button

Zone

Button

Hold

Button

Time (+/-)

Button

Schedule & Vacation

Program Buttons

Up/Down

Scroll Buttons

ZONE

A04038

Fig. 15 -- Functional Overview

Power Up Sequence

This section addresses initial power up (or commissioning) of a

new Evolution Zone Control. The User Interface will communicate

and identify all Evolution components in the system. The
following

is a typical example for a communicating

Variable--Speed Furnace / Fan Coil with a 2--stage Air Conditioner
/ Heat Pump (including Hybrid Heat).
The User Interface display will light up and indicate that it is now

“ESTABLISHING COMMUNICATIONS WITH EQUIPMENT
PLEASE WAIT”. The User Interface will automatically continue

by

“SEARCHING

FOR

EQUIPMENT”,

followed

by

“SEARCHING FOR OUTDOOR EQUIPMENT” (See Fig. 16).

BBU

IZ

01

--

B

Содержание EVOLUTION Zone Control SYSTXBBUIZ01-B

Страница 1: ...all local electrical codes during installation All wiring must conform to local and national electrical codes Improper wiring or installation may damage the Evolution Zone System Recognize safety info...

Страница 2: ...indoor unit outdoor unit and accessories accord ing to their instructions S Wire complete system according to this instruction S Setup commission and operate system according to this instruction to as...

Страница 3: ...the elements The Damper Control Module and zone dampers may be installed in any area where the temperature remains between 4_F to 158_F 20_C to 70_C and there is no condensation The cover must be inst...

Страница 4: ...essed Mount Interlocking Tabs 4 Recessed terminal block in wall 11 2 38 1 mm wide by 21 8 54 mm high A07150 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4 A03191 Fig...

Страница 5: ...CAL OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation Improper wiring of the ABCD connector will cause the Evolution Zone System to operate improperl...

Страница 6: ...olation relay coil to furnace or fan coil HUM and COM terminals will allow the Evolution Zone Control to automatically energize the HUM output during a call for humidification The N O relay contacts w...

Страница 7: ...AC and the electric heater is not self identifying ELECTRIC HEATER NOT IDENTIFIED will appear See Fig 18 Press either Time or Temp buttons to select appropriate size of electric heater installed then...

Страница 8: ...Press right side button to start Duct Assessment Duct Assessment will measure the relative size of the ductwork up to and through the dampers These measurements are used to control the correct amount...

Страница 9: ...one schedule to other zones us ing NO or YES 11 Exit the scheduling mode by either closing the door or pressing the SCHEDULE button 12 If changes are made you will be asked to SAVE CHANGES YES NO INST...

Страница 10: ...ll settings in Install Service menus to factory default settings Last 10 System Events S Yes No to reset last 10 system events under Service Info menu Setup Furnace Upon a first time start up of the E...

Страница 11: ...midify mode is increased to reduce duct and register sweating Also increases minimum airflow during normal cooling opera tion to reduce duct sweating Heater Size S choices dependent upon fan coil mode...

Страница 12: ...er run time Airflow Limits Since bypass damper is prohibited in this system this setting is used to select the maximum allowable noise airflow relationship into each zone based on air noise and comfor...

Страница 13: ...e if the AC heat pump is a 2 stage model runs low speed only CHECKOUT MENUS CHECKOUT FURNACE HEAT PUMP HEATING HEAT PUMP COOLING HUMIDIFIER VENTILATOR BACK SELECT A03204 Fig 33 Checkout Menu The Check...

Страница 14: ...MEDIUM S HIGH default S MAXIMUM Because there is no bypass damper the Zone Airflow Limit check will allow the installer to assess the airflow noise generated by the system providing the maximum amoun...

Страница 15: ...er Control Module sensor will read leaving air temperature of the indoor unit The temperature information is for display purposes only The system does not react to this temperature reading Outdoor Coi...

Страница 16: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Страница 17: ...a Equipment stage down or shut off if necessary b Fault history will record an event of AIRFLOW LIM ITED STAGEDOWN OCCURRED on stagedown and EXCESS STATIC PRESSURE if shut down c If shut down occurs o...

Страница 18: ...e a mistake on the start up screens and hit the right side button to get to the run mode How do I get back to start up 1 Press the ADVANCED button for at least 10 seconds 2 Install Service menu will a...

Страница 19: ...r Fault cooling mode only ventilator humidifier dehumidifier outdoor unit will be turned off Code 45 Control Circuitry Lockout NOTE For codes 13 14 and 21 the system will use heat pump heating exclusi...

Страница 20: ...nge at any time specifications or designs without notice and without incurring obligations E2007 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in China Edition Date 03...

Отзывы: