background image

18

TROUBLESHOOTING

Please refer to the Troubleshooting Guide available on HVAC Partners for more detail.

Evolution Zone Control does not power up.

1. Recheck wiring to ABCD on all devices.
2. Make sure all colors match for every terminal.
3. Make sure power is applied to the indoor unit, and the amber LED is lit on indoor control circuit board.
4. Check for 24VAC between the C and D terminals at Evolution Zone Control terminal connector and Damper Control Module.
5. Check fuse on indoor unit’s circuit board.

Display says “Indoor Unit Not Found”

1. Recheck wiring to ABCD on all devices.
2. Make sure all colors match for every terminal.
3. Press left--side button to try again.
4. If display still reads “Indoor Unit Not Found”, disconnect accessories and all devices from ABCD and connect User Interface directly

to indoor unit with a short piece of thermostat wire. Add other devices one at a time to determine where the communication issue
exists.

Display says “Outdoor Unit Not Found”, and I have a two--stage communicating outdoor unit.

1. Recheck wiring to ABCD connector on outdoor unit.
2. Make sure all colors match for every terminal.
3. Check for 24VAC between the C and D terminal connector of outdoor unit.

I made a mistake on the start--up screens, and hit the right--side button to get to the run mode. How do I get back to start--up?

1. Press the ADVANCED button for at least 10 seconds.
2. Install/Service menu will appear.
3. Scroll down to the INSTALL selection.
4. Press the right--side button; the screen will prompt you to press the right side again to re--install the system.

Control does not see zones 5 through 8.

1. Make sure zone module 5 -- 8 has the DIP switches set to the right.
2. Recheck wiring to the ABCD connectors.

Control says I have zones 5 -- 8 but not 1 -- 4.

1. Make sure zone module 1 -- 4 has the DIP switches set to the left.
2. Recheck wiring to the ABCD connectors.

Some zones in my zoned system do not provide enough comfort. (A noticeable difference exists between the actual room temperature
and operating setpoint, yet the equipment does not turn on).

1. The zone airflow limit may be set too low. Perform the Zone Airflow Limit Checkout procedure, raise airflow limit setting, if possible.

Some zones provide too much airflow and are noisy.

1. The zone airflow limit may be set too high. Perform the Zone Airflow Limit Checkout procedure, lower airflow limit setting if pos-

sible.

To check current system status.

1. Press and hold the right side button for 3 seconds. This will display the current active system faults.
2. If no faults are active, the Status screen will show status of each component in the system.

BBU

IZ

01

--

B

Содержание EVOLUTION Zone Control SYSTXBBUIZ01-B

Страница 1: ...all local electrical codes during installation All wiring must conform to local and national electrical codes Improper wiring or installation may damage the Evolution Zone System Recognize safety info...

Страница 2: ...indoor unit outdoor unit and accessories accord ing to their instructions S Wire complete system according to this instruction S Setup commission and operate system according to this instruction to as...

Страница 3: ...the elements The Damper Control Module and zone dampers may be installed in any area where the temperature remains between 4_F to 158_F 20_C to 70_C and there is no condensation The cover must be inst...

Страница 4: ...essed Mount Interlocking Tabs 4 Recessed terminal block in wall 11 2 38 1 mm wide by 21 8 54 mm high A07150 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4 A03191 Fig...

Страница 5: ...CAL OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation Improper wiring of the ABCD connector will cause the Evolution Zone System to operate improperl...

Страница 6: ...olation relay coil to furnace or fan coil HUM and COM terminals will allow the Evolution Zone Control to automatically energize the HUM output during a call for humidification The N O relay contacts w...

Страница 7: ...AC and the electric heater is not self identifying ELECTRIC HEATER NOT IDENTIFIED will appear See Fig 18 Press either Time or Temp buttons to select appropriate size of electric heater installed then...

Страница 8: ...Press right side button to start Duct Assessment Duct Assessment will measure the relative size of the ductwork up to and through the dampers These measurements are used to control the correct amount...

Страница 9: ...one schedule to other zones us ing NO or YES 11 Exit the scheduling mode by either closing the door or pressing the SCHEDULE button 12 If changes are made you will be asked to SAVE CHANGES YES NO INST...

Страница 10: ...ll settings in Install Service menus to factory default settings Last 10 System Events S Yes No to reset last 10 system events under Service Info menu Setup Furnace Upon a first time start up of the E...

Страница 11: ...midify mode is increased to reduce duct and register sweating Also increases minimum airflow during normal cooling opera tion to reduce duct sweating Heater Size S choices dependent upon fan coil mode...

Страница 12: ...er run time Airflow Limits Since bypass damper is prohibited in this system this setting is used to select the maximum allowable noise airflow relationship into each zone based on air noise and comfor...

Страница 13: ...e if the AC heat pump is a 2 stage model runs low speed only CHECKOUT MENUS CHECKOUT FURNACE HEAT PUMP HEATING HEAT PUMP COOLING HUMIDIFIER VENTILATOR BACK SELECT A03204 Fig 33 Checkout Menu The Check...

Страница 14: ...MEDIUM S HIGH default S MAXIMUM Because there is no bypass damper the Zone Airflow Limit check will allow the installer to assess the airflow noise generated by the system providing the maximum amoun...

Страница 15: ...er Control Module sensor will read leaving air temperature of the indoor unit The temperature information is for display purposes only The system does not react to this temperature reading Outdoor Coi...

Страница 16: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Страница 17: ...a Equipment stage down or shut off if necessary b Fault history will record an event of AIRFLOW LIM ITED STAGEDOWN OCCURRED on stagedown and EXCESS STATIC PRESSURE if shut down c If shut down occurs o...

Страница 18: ...e a mistake on the start up screens and hit the right side button to get to the run mode How do I get back to start up 1 Press the ADVANCED button for at least 10 seconds 2 Install Service menu will a...

Страница 19: ...r Fault cooling mode only ventilator humidifier dehumidifier outdoor unit will be turned off Code 45 Control Circuitry Lockout NOTE For codes 13 14 and 21 the system will use heat pump heating exclusi...

Страница 20: ...nge at any time specifications or designs without notice and without incurring obligations E2007 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in China Edition Date 03...

Отзывы: