This menu has several layers, allowing modification of equipment
settings. No settings will need to be made at equipment (i.e. DIP
switches on a furnace). All configuration settings made effective
from this menu will override equipment configuration made by dip
switches. Fig. 27 shows all the information that can be found in the
SETUP
menu.
Setup -- Thermostat
Auto Mode Setup:
S
Enable/Disable Auto Changeover mode (default=En-
able).
S
Auto Changeover Time may be adjusted 5 to 120 min-
utes, (default = 30 minutes).
When Auto mode is enabled (factory default) a change from heat
to cool (or vice versa) will not occur until an opposite mode
demand has existed for 30 minutes. If the setpoint is changed, the
30 minute timer is deleted.
Heat/Cool Deadband:
S
0 to 6
_
F / 0 to 3.3
_
C, (default = 2
_
F / 1.1
_
F).
The minimum difference enforced between heating and cooling
desired temperatures. This can allow one setting to “push” the
other to maintain this difference.
Offsets:
This option allows calibration (or deliberate miscalibration) of the
temperature and humidity sensors. These offsets are added to the
actual temperature/humidity values (defaults=0).
S
Zone 1 Offset: --5 to +5
_
F (--2.8
_
C to +2.8
_
C).
S
Outside Temp Offset: --5 to +5
_
F (--2.8
_
C to +2.8
_
C).
S
Humidity Offset: --10 to +10%.
Cycles Per Hour:
S
Maximum cycles per hour = 4 (default) or 6.
S
Anticipator = 1 to 9 (default=3). This adjusts sensitivity
to temperature changes. 1 = most sensitive, 9 = least sen-
sitive.
S
If space is over--conditioning, increase the anticipator
setting.
S
If space is under--conditioning, decrease the anticipator
setting.
Programming:
S
ON (default)-- allows program schedule to be set by user.
S
OFF -- system becomes non--programmable
S
Periods Per Day = 2 or 4 (default=4)
S
Programmable Fan On/Off (default=Off). If ON is se-
lected, fan can be set to Auto, Low, Med, or High.
Smart Recovery:
S
On or Off (default=On)
Applies to programmable operation only. Will start recovery 90
minutes prior to schedule change in both heating and cooling
mode. Refer to operational information for more detail.
English/Metric Display:
S
_
F or
_
C (default =
_
F)
Reset Factory Defaults:
Program Schedule:
S
Yes/No to reset back to Energy Star default Time and
Temp schedules.
User Settings:
S
Yes/No to reset the user settings in the Advanced Setup
to factory default settings.
Install Settings:
S
Yes/No to reset install settings in Install/Service menus to
factory default settings.
Last 10 System Events:
S
Yes/No to reset last 10 system events under Service Info
menu.
Setup -- Furnace
Upon a first time start--up of the Evolution Zone Control, the
furnace DIP switch settings will be copied to the furnace setup
menu. Any changes can then be made from the Evolution Zone
Control.
Airflow:
S
COMFORT (default)
S
EFFICIENCY
Selects the airflow of the furnace when heating.
EFFICIENCY
is
the airflow used to meet specified ratings,
COMFORT
is a
decreased airflow used to increase the output air temperature and
provide increased comfort.
AC Airflow:
S
COMFORT (default) -- cooling airflow is varied depend-
ing on humidity and temperature demands settings. This
selection enables the full dehumidify and comfort capa-
bilities of the system. When COMFORT is not selected,
the unit will not run reduced aiflows for dehumidifica-
tion.
S
EFFICIENCY -- fixed airflow used to achieve specified
ratings -- no dehumidification airflow reduction. This is
nominally 350 CFM/ton, but will vary if a 2--stage out-
door unit is used.
S
MAXIMUM -- 400 CFM/ton.
Dehum Airflow:
S
NORMAL (factory default) -- When equipment is run-
ning to dehumidify, the airflow is allowed to adjust to a
minimum to satisfy the dehumidification call.
S
HIGH -- Minimum airflow during the dehumidify mode
is increased to reduce duct and register sweating. Also
increases minimum airflow during normal cooling opera-
tion to reduce duct sweating.
Low Heat Rise
S
ON
S
OFF (default)
Set to
ON
if the system contains a bypass humidifier. The
ON
setting will increase the furnace low heat airflow.
Staging
S
SYSTEM (default)
S
LOW
S
HIGH
Controls the staging of the furnace.
SYSTEM
setting will allow
the Evolution Zone Control to determine furnace staging.
LOW
will only run the low stage of furnace heat.
HIGH
will only run
the high stage of furnace heat.
G Terminal
This setup option selects desired operation when the R--G circuit
changes state on the furnace control board depending on setup.
S
DISABLED (Default)
S
FAN -- turns on fan to selected fan speed when G termi-
nal is energized. See Fig. 28.
S
FAN SPEED -- select Low, Med, High for all zones
when G terminal is energized
S
SHUTDOWN -- shuts off fan and equipment when initi-
ated. This function may be activated by a dry contact
from an external device such as a float switch or a relay.
User selects whether the contact is NC -- normally closed
(default) or NO -- normally open. User Interface displays
SYSTEM MALFUNCTION on screen and registers G
BBU
IZ
01
--
B