background image

2

INTRODUCTION

The Evolution Zone System consists of several intelligent
communicating components which includes the Evolution Zone

Control (or User Interface), Smart Sensors, Damper Control
Module, variable speed furnace or FE fan coil, 2--stage AC or HP

and Evolution Packaged Products, which continually communicate

with each other via a four--wire connection called the ABCD bus.
Commands, operating conditions, and other data are passed

continually between components over the ABCD bus. The result is
a new level of comfort, versatility, and simplicity.
All Evolution furnaces or fan coils are variable--speed and
multi--stage for maximum flexibility, efficiency, and comfort. They

support controlled ventilation, humidification, dehumidification,

and

air quality

control.

Either an

Evolution

2--stage

(communicating), or a standard 24VAC controlled outdoor unit

may be used.
When using conventional outdoor units, the Evolution furnace or

fan coil provides the 24 volt signals needed to control them. Also,

the Evolution Damper Control Module (P/N SYSTXBB4ZC01)
allows connection of a Bryant HRV or ERV without the need for a

separate wall control.
All system components are controlled through the wall mounted

Evolution Zone Control, which replaces the conventional

thermostat and provides the homeowner with a single wall control
for all features of the system.

Design Considerations

The Evolution Zone system is unique because a bypass damper
must not be used. This is possible due to the intelligence of the

system and variable speed motor technology. For trouble--free

applications, the following parameters should always be met:

1. Zones should be sized so that each zone can deliver at least

the minimum airflow for the system in both heating and
cooling modes.

2. Oversize duct work by 25% to avoid excess noise at mini-

mum zone airflow.

3. Be aware that heating airflow may be higher than cooling

airflow depending on equipment combination.

INSTALLATION AND START--UP

OVERVIEW

This instruction covers installation of the Evolution Zone Control

only

. Physical installation instructions for the indoor and outdoor

equipment, Damper Control Module, and accessories are provided

with each unit.
Setup, commissioning, operation, and troubleshooting of the

Evolution Zone System are covered in this installation instruction.
It is the guide to connecting the system components and

commissioning the system once all physical components are

installed. Special screen prompts and start--up capabilities are
provided in the Evolution System to simplify and automate the

initial commissioning of the system.

S

Install Evolution Zone Control according to this instruc-

tion.

S

Install indoor unit, outdoor unit, and accessories accord-

ing to their instructions.

S

Wire complete system according to this instruction.

S

Setup, commission, and operate system according to this

instruction to assure a smooth and trouble free start--up.

INSTALLATION

Check Equipment and Job Site

Inspect equipment. File claim with shipping company prior to
installation if shipment is damaged or incomplete.

Evolution Zone Control Location and Wiring

Considerations

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal injury

or death.
Disconnect power before routing control wiring.

!

WARNING

All wiring must comply with national, local, and state codes.

Evolution Zone Control Location

The Evolution Zone Control User Interface is the command center

for the Evolution Zone System and is typically located in Zone 1 to
sense and control temperature in this zone. It should be located

where it is easily accessible and visible to the adult homeowner or
end user.
For accurate temperature measurement, the following guidelines
should be followed:
The Evolution Zone Control and Room Sensors should be

mounted:

S

Approximately 5 feet (1.5 meters) from the floor.

S

Close to or in a frequently used room, preferably on an
inside partitioning wall.

S

On a section of wall without pipes or ductwork.

The Evolution Zone Control and Room Sensors should

NOT

be

mounted:

S

Close to a window, on an outside wall, or next to a door
leading to the outside.

S

Exposed to direct light or heat from a lamp, sun, fire-
place, or other temperature--radiating objects which

could cause a false reading.

S

Close to or in direct airflow from supply registers.

S

In areas with poor air circulation, such as behind a door
or in an alcove.

Remote Room Sensor Option

A Remote Room Sensor can be used with the Evolution Zone
Control to take the place of the User Interface internal temperature

sensor. This allows the Evolution Zone Control to be mounted in
areas with less than optimal airflow (such as near an exterior door,

window or in a closet). The remote sensor can be wired to the

terminal block connectors labeled S1 and S2 at the User Interface
backplate, or the OS1 and OS1C connection at the Damper Control

Module. In either case, the Evolution Zone Control will
automatically detect the Remote Room Sensor and ignore its

internal temperature sensor. It is also important to note the

humidity sensor cannot be remotely located, so do not locate the
Evolution Zone Control in an area where humidity sensing may

not be accurate.

NOTE

: S1 & S2 connection on User Interface backplate is now

used for Remote Room Sensor, NOT for OAT Sensor hookup.
In addition, the Remote Room Sensor is a temperature sensor only,

having no additional user inputs. This sensor is typically connected
to the Damper Control Module and used to sense and control

temperature in each zone.

BBU

IZ

01

--

B

Содержание EVOLUTION Zone Control SYSTXBBUIZ01-B

Страница 1: ...all local electrical codes during installation All wiring must conform to local and national electrical codes Improper wiring or installation may damage the Evolution Zone System Recognize safety info...

Страница 2: ...indoor unit outdoor unit and accessories accord ing to their instructions S Wire complete system according to this instruction S Setup commission and operate system according to this instruction to as...

Страница 3: ...the elements The Damper Control Module and zone dampers may be installed in any area where the temperature remains between 4_F to 158_F 20_C to 70_C and there is no condensation The cover must be inst...

Страница 4: ...essed Mount Interlocking Tabs 4 Recessed terminal block in wall 11 2 38 1 mm wide by 21 8 54 mm high A07150 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4 A03191 Fig...

Страница 5: ...CAL OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation Improper wiring of the ABCD connector will cause the Evolution Zone System to operate improperl...

Страница 6: ...olation relay coil to furnace or fan coil HUM and COM terminals will allow the Evolution Zone Control to automatically energize the HUM output during a call for humidification The N O relay contacts w...

Страница 7: ...AC and the electric heater is not self identifying ELECTRIC HEATER NOT IDENTIFIED will appear See Fig 18 Press either Time or Temp buttons to select appropriate size of electric heater installed then...

Страница 8: ...Press right side button to start Duct Assessment Duct Assessment will measure the relative size of the ductwork up to and through the dampers These measurements are used to control the correct amount...

Страница 9: ...one schedule to other zones us ing NO or YES 11 Exit the scheduling mode by either closing the door or pressing the SCHEDULE button 12 If changes are made you will be asked to SAVE CHANGES YES NO INST...

Страница 10: ...ll settings in Install Service menus to factory default settings Last 10 System Events S Yes No to reset last 10 system events under Service Info menu Setup Furnace Upon a first time start up of the E...

Страница 11: ...midify mode is increased to reduce duct and register sweating Also increases minimum airflow during normal cooling opera tion to reduce duct sweating Heater Size S choices dependent upon fan coil mode...

Страница 12: ...er run time Airflow Limits Since bypass damper is prohibited in this system this setting is used to select the maximum allowable noise airflow relationship into each zone based on air noise and comfor...

Страница 13: ...e if the AC heat pump is a 2 stage model runs low speed only CHECKOUT MENUS CHECKOUT FURNACE HEAT PUMP HEATING HEAT PUMP COOLING HUMIDIFIER VENTILATOR BACK SELECT A03204 Fig 33 Checkout Menu The Check...

Страница 14: ...MEDIUM S HIGH default S MAXIMUM Because there is no bypass damper the Zone Airflow Limit check will allow the installer to assess the airflow noise generated by the system providing the maximum amoun...

Страница 15: ...er Control Module sensor will read leaving air temperature of the indoor unit The temperature information is for display purposes only The system does not react to this temperature reading Outdoor Coi...

Страница 16: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Страница 17: ...a Equipment stage down or shut off if necessary b Fault history will record an event of AIRFLOW LIM ITED STAGEDOWN OCCURRED on stagedown and EXCESS STATIC PRESSURE if shut down c If shut down occurs o...

Страница 18: ...e a mistake on the start up screens and hit the right side button to get to the run mode How do I get back to start up 1 Press the ADVANCED button for at least 10 seconds 2 Install Service menu will a...

Страница 19: ...r Fault cooling mode only ventilator humidifier dehumidifier outdoor unit will be turned off Code 45 Control Circuitry Lockout NOTE For codes 13 14 and 21 the system will use heat pump heating exclusi...

Страница 20: ...nge at any time specifications or designs without notice and without incurring obligations E2007 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in China Edition Date 03...

Отзывы: