background image

13

Setup -- Accessories

Filter Type:

S

MEDIA (i.e. TrueSense

t

)

S

EAC

S

MEDIA+EAC (i.e. TrueSense

t

)

CLEAN INTERVAL: 30 to 180 days (of actual blower operation).

(Default = 90)
Interval at which the Clean Filter notification will turn on. Applies
to EAC filter selection only.

Humidifier Installed:

S

NO

S

YES

If YES, indicates to the system whether a humidifier is installed

and enables humidification functions.
CHANGE PAD INTERVAL: 1 to 24 months (default=12 months)
Interval at which the Change Humidify Pad notification will be
displayed.
HUMIDIFY WITH FAN:

S

NO (default)

S

YES

If YES, the humidifier will turn on if there is a humidify demand

present. The fan will turn on to Low speed if the fan setting is

Auto.

Ventilator:
NOTE

: Only appears if ventilator is installed.

CLEAN INTERVAL:

S

60 to 180 days of actual operation (default=90)

Interval at which the Clean Ventilator Pre--filter notification will
turn on.

UV Lights Installed

S

NO

S

YES

If YES, indicates to the system whether UV lights are installed.
CHANGE INTERVAL:

S

6 to 48 months operation time (default=12 months)

Interval at which the Change UV Lights notification will be
displayed.

Setup -- System Maintenance

Remind Owner of Routine Maintenance Every:

This setup is used to adjust the timer interval in which the normal

System Maintenance notification is turned on for the homeowner.
Range =

S

OFF

S

6 to 24 months, (default=12 months) Pressing the right
side button will reset the timer. Pop--up confirmation will
be shown.

 

SYSTEM  MAINTENANCE

< BACK

REMIND OWNER OF
MAINTENANCE EVERY:

12  MONTHS

% USED:

50%

RESET >

A07033

Fig. 32 -- System Maintenance

Setup -- Utility Saver

Cooling/Heat Pump Heating:

S

Turn off, Low Stage

This setup is available only if the equipment has a utility saver
input (refer to equipment Installation Instructions.) This setup

controls the response of the equipment when the utility saver input
is active.
The choices include:

S

Turn Off , (equipment turns off)

S

Low Stage (available if the AC/heat pump is a 2--stage
model, runs low speed only)

CHECKOUT MENUS

CHECKOUT

FURNACE

HEAT PUMP HEATING

HEAT PUMP COOLING

HUMIDIFIER

VENTILATOR

   BACK               SELECT

A03204

Fig. 33 -- Checkout Menu

The Checkout menu will show the equipment installed in the

system. A sample checkout menu is shown in Fig. 33.

Checkout -- Furnace or Gas PAC

Make sure the furnace is properly installed before continuing.

S

LOW HEAT RUNTIME: 5 min.

S

HIGH HEAT RUNTIME: 5 min.

This menu item allows the furnace to be exercised. First, a low heat
runtime and high heat runtime are selected. Range = 5 -- 120 min.
If only the low heat is to be exercised:
The furnace will execute its ignition start--up sequence. This
sequence will be displayed on the Evolution Zone Control screen.

After the gas valve and blower motor turn on, the screen will
automatically change to “

FURNACE CHECK

” and show the

current operating status of the furnace.

Checkout -- Electric Heat

S

ELECTRIC HEAT RUNTIME: 5 min., Default time = 5
min., Range = 0 -- 120 min.

If you have a fan coil with electric heaters, this menu item will
allow the heaters to be exercised.
With self--identifying electric heaters, three stages of electric heat
are available to be exercised in any combination. Non--identifying

heaters will only provide one stage of heat.
Enter the run time (in minutes) of each stage of heat to be exercised
then press START (right--side button). The display will change to

show the fan coil’s operating status.

Checkout -- Heat Pump Heating

S

HIGH HEAT RUNTIME: 5 min.

S

LOW HEAT RUNTIME: 5 min.

S

DEFROST: NO

The heat pump heating mode can be exercised with this menu
option. With a 2--stage heat pump, a low heat runtime and a high

heat runtime are independently selectable to exercise. A defrost

cycle is also selectable. Default time = Fixed 5 min. minimum,
range = 5 -- 120 min.

NOTE

:

Airflows during Checkout modes are fixed to the

Efficiency setting and are independent of other airflow settings. To
view airflows for normal heat pump heating mode, exit the
Checkout screen and apply a heating demand to the system.

Checkout -- Heat Pump Cooling or AC Cooling

S

HIGH COOL RUNTIME: 5 min.

S

LOW COOL RUNTIME: 5 min.

BBU

IZ

01

--

B

Содержание EVOLUTION Zone Control SYSTXBBUIZ01-B

Страница 1: ...all local electrical codes during installation All wiring must conform to local and national electrical codes Improper wiring or installation may damage the Evolution Zone System Recognize safety info...

Страница 2: ...indoor unit outdoor unit and accessories accord ing to their instructions S Wire complete system according to this instruction S Setup commission and operate system according to this instruction to as...

Страница 3: ...the elements The Damper Control Module and zone dampers may be installed in any area where the temperature remains between 4_F to 158_F 20_C to 70_C and there is no condensation The cover must be inst...

Страница 4: ...essed Mount Interlocking Tabs 4 Recessed terminal block in wall 11 2 38 1 mm wide by 21 8 54 mm high A07150 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4 A03191 Fig...

Страница 5: ...CAL OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation Improper wiring of the ABCD connector will cause the Evolution Zone System to operate improperl...

Страница 6: ...olation relay coil to furnace or fan coil HUM and COM terminals will allow the Evolution Zone Control to automatically energize the HUM output during a call for humidification The N O relay contacts w...

Страница 7: ...AC and the electric heater is not self identifying ELECTRIC HEATER NOT IDENTIFIED will appear See Fig 18 Press either Time or Temp buttons to select appropriate size of electric heater installed then...

Страница 8: ...Press right side button to start Duct Assessment Duct Assessment will measure the relative size of the ductwork up to and through the dampers These measurements are used to control the correct amount...

Страница 9: ...one schedule to other zones us ing NO or YES 11 Exit the scheduling mode by either closing the door or pressing the SCHEDULE button 12 If changes are made you will be asked to SAVE CHANGES YES NO INST...

Страница 10: ...ll settings in Install Service menus to factory default settings Last 10 System Events S Yes No to reset last 10 system events under Service Info menu Setup Furnace Upon a first time start up of the E...

Страница 11: ...midify mode is increased to reduce duct and register sweating Also increases minimum airflow during normal cooling opera tion to reduce duct sweating Heater Size S choices dependent upon fan coil mode...

Страница 12: ...er run time Airflow Limits Since bypass damper is prohibited in this system this setting is used to select the maximum allowable noise airflow relationship into each zone based on air noise and comfor...

Страница 13: ...e if the AC heat pump is a 2 stage model runs low speed only CHECKOUT MENUS CHECKOUT FURNACE HEAT PUMP HEATING HEAT PUMP COOLING HUMIDIFIER VENTILATOR BACK SELECT A03204 Fig 33 Checkout Menu The Check...

Страница 14: ...MEDIUM S HIGH default S MAXIMUM Because there is no bypass damper the Zone Airflow Limit check will allow the installer to assess the airflow noise generated by the system providing the maximum amoun...

Страница 15: ...er Control Module sensor will read leaving air temperature of the indoor unit The temperature information is for display purposes only The system does not react to this temperature reading Outdoor Coi...

Страница 16: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Страница 17: ...a Equipment stage down or shut off if necessary b Fault history will record an event of AIRFLOW LIM ITED STAGEDOWN OCCURRED on stagedown and EXCESS STATIC PRESSURE if shut down c If shut down occurs o...

Страница 18: ...e a mistake on the start up screens and hit the right side button to get to the run mode How do I get back to start up 1 Press the ADVANCED button for at least 10 seconds 2 Install Service menu will a...

Страница 19: ...r Fault cooling mode only ventilator humidifier dehumidifier outdoor unit will be turned off Code 45 Control Circuitry Lockout NOTE For codes 13 14 and 21 the system will use heat pump heating exclusi...

Страница 20: ...nge at any time specifications or designs without notice and without incurring obligations E2007 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in China Edition Date 03...

Отзывы: