12
S
60 minutes
S
90 minutes
S
120 minutes (default)
S
Auto--Defrost interval optimized by outdoor control (de-
fault for communicating HP)
Time interval at which defrost cycles can occur on a heat pump.
Elect Heat Lockout
S
NONE (default)
S
+5 to 55
_
F / --15 to 18
_
C
Outside temperature above which the electric heat will not operate
except for defrost.
High Cool Latch:
S
NONE (default)
S
80 to 110
_
F / 27 to 43
_
C
Outside temperature above which only the high speed (of a 2--stage
outdoor unit) will run when cooling.
High Heat Latch
S
OFF (default)
S
20 to 50
_
F / --7 to 10
_
C 2 --stage heat pump runs only
high stage heating below a selectable outdoor tempera-
ture. Selections from 20 to 50
_
F / --7 to 10
_
C are avail-
able in 5
_
F / 2.8
_
C increments.
Setup -- Hybrid Heat
HYBRID HEAT SETUP
FURNACE
LOCKOUT:
> 30 F
HEAT PUMP
LOCKOUT:
< 15 F
DEFROST W/FURNACE:
YES
< BACK
HP TO FURNACE
STAGE TIME:
15 MIN
OUTSIDE LOCKOUT TEMPS
A07030
Fig. 30 -- Hybrid Heat Setup
FURNACE LOCKOUT -- Temperature above which the furnace
will not operate, except for defrost.
S
Default = NONE
S
Available settings = NONE thru >55
_
F / 13
_
C
HEAT PUMP LOCKOUT -- Temperature below which the heat
pump will not operate.
S
Default = NONE
S
Available settings = NONE thru <55
_
F / 13
_
C
DEFROST W/FURNACE -- Choose whether furnace operates
during defrost cycle
S
Default = YES
S
Available settings = YES / NO
HP TO FURNACE STAGING TIME -- Adjust the minimum
amount of time high stage heat pump will run before furnace will
be allowed to run.
S
Default = 15 MIN
S
Available settings = 15--60 minutes
Setup -- Zoning
Disable Zoning:
S
NO (default)
S
YES
If YES is selected, zoning is disabled and all dampers open. The
system will run un--zoned using the Zone 1 sensor.
Zone Offsets:
S
Zone Temperature Offsets (default = 0) Range --5
_
F to
+5
_
F / --2.8
_
C to +2.8
_
C
This option allows actual temperature offset for each zone,
allowing calibration (or deliberate miscalibration) of each sensor.
Humidifier interval is time only, not actual humidifier run time.
Airflow Limits:
Since bypass damper is prohibited in this system, this setting is
used to select the maximum allowable noise/airflow relationship
into each zone based on air noise and comfort requirements. For
setup guidelines, see Airflow Limits Checkout in the next section.
S
Low -- 100% of maximum assessed airflow
S
Medium -- 150% of maximum assessed airflow
S
High (default) -- 200% of maximum assessed airflow
S
Maximum -- no limit
Assessed airflow is determined as described in DUCT
ASSESSMENT.
Duct Assessment Time
1 p.m. (default), adjustable in 1 hour increments from 1 p.m. to 12
AM (24 hours). Select which hour of the day the duct assessment
will be performed.
Setup -- Hydronic Heat
HYDRONIC HEAT SETUP
AIRFLOW:
800 CFM
BLOWER ON DELAY:
30 SEC
HOT WATER
LOCKOUT:
> 30 F
HEAT PUMP
LOCKOUT:
< 45 F
DEFROST W/WATER:
YES
BLOWER OFF DELAY: 30 SEC
< BACK
A07031
Fig. 31 -- Hydronic Heat Setup
HOT WATER LOCKOUT -- Outside temperature above which the
hot water will not operate except for defrost (if selected).
S
Available settings -- NO, 5 to 55
_
F / --15 to 13
_
C in 1
_
F
/ .6
_
C increments
HEAT PUMP LOCKOUT -- Outside temperature below which the
heat pump will not operate, 1
_
F / .6
_
C resolution.
S
Appears only with a heat pump outdoor unit.
S
Available settings -- NO, 5 to 55
_
F / --15 to 13
_
C in 1
_
F
/ .6
_
C increments
DEFROST W/WATER:
S
Available settings: YES / NO (Default =YES)
S
Appears only if heat pump is available. If no, hot water
will not run during a defrost.
AIRFLOW -- Selects desired airflow during Hydronic Heating
S
Available range from OFF, 500 CFM(minimum) to 400
CFM/ton cooling maximum in 50 CFM increments.
S
Default is the cooling airflow. (350 CFM/ton)
S
OFF selection does not turn off airflow if heat pump is
defrosting.
BLOWER ON DELAY -- Time after hot water is requested that the
blower will turn on.
S
Available settings -- 0 to 240 seconds in 30 second incre-
ments
S
Default is 30
S
Does not appear if a heat pump is present since heat
pump and hot water run simultaneously.
BLOWER OFF DELAY-- Time after hot water request terminates
before the blower will turn off.
S
Available settings -- 0 to 240 seconds in 30 second incre-
ments
S
Default is 0
BBU
IZ
01
--