background image

5

INSTALLING EVOLUTION ZONE

CONTROL

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Before installing Evolution Zone Control, turn off all power

to equipment. There may be more than one power source to

disconnect.

!

WARNING

1. Turn off all power to equipment.
2. If an existing User Interface or control is being replaced:

a. Remove existing control from wall.

b. Disconnect wires from existing control.

c. Discard or recycle old control.

NOTE

: Mercury is a hazardous waste, if existing control contains

any mercury, it MUST be disposed of properly. The User Interface
does not contain mercury.

3. Select Evolution Zone Control mounting plastic (recess

mount or surface mount and decorative backplate if de-
sired).

4. Route wires through large hole in mounting plastic. Level

rear plastic against wall (for aesthetic value only -- Evolu-
tion Zone Control need not be level to operate properly) and

mark wall through two mounting holes.

5. Drill two 3/16” (4.8 mm) mounting holes in wall where

marked.

6. Secure mounting plastic to wall using two screws and an-

chors provided.

7. Adjust length and routing of each wire to reach each wire

entry on the connector backplate. Strip 1/4” (6.4 mm) of in-

sulation from each wire.

8. Match and connect thermostat wires to proper terminals on

User Interface backplate. See wiring diagram Fig. 12, 13,

and 14.

A — Green = Data A
B — Yellow = Data B
C — White = 24VAC (Com)
D — Red = 24VAC (Hot)

NOTE

: It is not mandatory that the above color code be used, but

each ABCD connection in the system MUST be wired consistently.
A separate ABCD Connector comes inside packaging and should
be used when connecting to furnace (or fan coil). Ensure connector
is inserted properly into circuit board. (See Fig. 11.)

A B C D

A03193

Fig. 11 -- Wire ABCD Connector

ELECTRICAL OPERATION HAZARD

Failure to follow this caution may result in equipment damage

or improper operation.
Improper wiring of the ABCD connector will cause the

Evolution Zone System to operate improperly. Check to make

sure all wiring is correct before proceeding with installation or

turning on power.

CAUTION

!

9. Push any excess wire into the wall. Seal hole in wall to pre-

vent any air leaks. Leaks can affect operation.

10. Attach Evolution Zone Control to the mounting plastic by

lining up the plastic guides on the back of the control with
the opening on the mounting plastic and push on.

11. Perform installation of all other system equipment (i.e.

dampers, humidifier, ventilator, UV lights, etc.)

12. Turn on power to equipment.

See wiring diagrams Fig. 12, 13, and 14 for connecting the
Evolution Zone Control and Smart Sensors to the Damper Control

Module. More information regarding Damper Control set--up and

wiring can be found in Damper Control Module Installation
Instructions.
See wiring diagram, Fig. 12, which includes an indoor
communicating furnace or FE fan coil, with a 2--stage Puron

r

refrigerant communicating outdoor unit. No additional OAT
(outdoor air temperature) sensor is required because the Evolution

Zone Control will use the temperature sensor inside the outdoor

unit.
See wiring diagram, Fig. 13, for connecting an indoor

communicating furnace or FE fan coil with a 1--stage air
conditioning unit (non--communicating outdoor). An Outdoor Air

Temperature (OAT) sensor may be installed (but is not required) at

the indoor furnace or fan coil OAT terminals. When OAT sensor is
applied, the Evolution System will provide enhanced system

features and benefits.
See wiring diagram Fig. 14 for connecting an FE fan coil with a

1--stage heat pump (non--communicating outdoor unit). When
OAT is applied, the Evolution System will provide enhanced

system features and benefits.

NOTE

: For other applications not listed, refer to the Network

Interface Module (NIM) Installation Instructions.

BBU

IZ

01

--

B

Содержание EVOLUTION Zone Control SYSTXBBUIZ01-B

Страница 1: ...all local electrical codes during installation All wiring must conform to local and national electrical codes Improper wiring or installation may damage the Evolution Zone System Recognize safety info...

Страница 2: ...indoor unit outdoor unit and accessories accord ing to their instructions S Wire complete system according to this instruction S Setup commission and operate system according to this instruction to as...

Страница 3: ...the elements The Damper Control Module and zone dampers may be installed in any area where the temperature remains between 4_F to 158_F 20_C to 70_C and there is no condensation The cover must be inst...

Страница 4: ...essed Mount Interlocking Tabs 4 Recessed terminal block in wall 11 2 38 1 mm wide by 21 8 54 mm high A07150 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4 A03191 Fig...

Страница 5: ...CAL OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation Improper wiring of the ABCD connector will cause the Evolution Zone System to operate improperl...

Страница 6: ...olation relay coil to furnace or fan coil HUM and COM terminals will allow the Evolution Zone Control to automatically energize the HUM output during a call for humidification The N O relay contacts w...

Страница 7: ...AC and the electric heater is not self identifying ELECTRIC HEATER NOT IDENTIFIED will appear See Fig 18 Press either Time or Temp buttons to select appropriate size of electric heater installed then...

Страница 8: ...Press right side button to start Duct Assessment Duct Assessment will measure the relative size of the ductwork up to and through the dampers These measurements are used to control the correct amount...

Страница 9: ...one schedule to other zones us ing NO or YES 11 Exit the scheduling mode by either closing the door or pressing the SCHEDULE button 12 If changes are made you will be asked to SAVE CHANGES YES NO INST...

Страница 10: ...ll settings in Install Service menus to factory default settings Last 10 System Events S Yes No to reset last 10 system events under Service Info menu Setup Furnace Upon a first time start up of the E...

Страница 11: ...midify mode is increased to reduce duct and register sweating Also increases minimum airflow during normal cooling opera tion to reduce duct sweating Heater Size S choices dependent upon fan coil mode...

Страница 12: ...er run time Airflow Limits Since bypass damper is prohibited in this system this setting is used to select the maximum allowable noise airflow relationship into each zone based on air noise and comfor...

Страница 13: ...e if the AC heat pump is a 2 stage model runs low speed only CHECKOUT MENUS CHECKOUT FURNACE HEAT PUMP HEATING HEAT PUMP COOLING HUMIDIFIER VENTILATOR BACK SELECT A03204 Fig 33 Checkout Menu The Check...

Страница 14: ...MEDIUM S HIGH default S MAXIMUM Because there is no bypass damper the Zone Airflow Limit check will allow the installer to assess the airflow noise generated by the system providing the maximum amoun...

Страница 15: ...er Control Module sensor will read leaving air temperature of the indoor unit The temperature information is for display purposes only The system does not react to this temperature reading Outdoor Coi...

Страница 16: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Страница 17: ...a Equipment stage down or shut off if necessary b Fault history will record an event of AIRFLOW LIM ITED STAGEDOWN OCCURRED on stagedown and EXCESS STATIC PRESSURE if shut down c If shut down occurs o...

Страница 18: ...e a mistake on the start up screens and hit the right side button to get to the run mode How do I get back to start up 1 Press the ADVANCED button for at least 10 seconds 2 Install Service menu will a...

Страница 19: ...r Fault cooling mode only ventilator humidifier dehumidifier outdoor unit will be turned off Code 45 Control Circuitry Lockout NOTE For codes 13 14 and 21 the system will use heat pump heating exclusi...

Страница 20: ...nge at any time specifications or designs without notice and without incurring obligations E2007 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in China Edition Date 03...

Отзывы: