background image

15

Static Press:

S

Inches of water. Displays calculated static pressure that
the furnace is currently experiencing.

S

If static pressure cannot be accurately calculated, the dis-
play will read UNKNOWN. When this is seen, the sys-

tem is adjusting to high static pressure by cutting back
blower RPM.

Lockout Timer:

S

Seconds

If a lockout timer is active, this will show the current time value.

See furnace manual for details on lockout timers.

Service -- Fan Coil Status

Electric Heat:

S

OFF, LOW, MED, HIGH

Displays stages of electric heat that the fan coil is currently

delivering.

Airflow CFM:

S

(fan coil model number dependent)

Cubic Feet per Minute of air the User Interface is currently

requesting.

Leaving Air Temp:
This sensor is NOT required

. However, if LAT sensor is

connected to the Damper Control Module, the sensor will read

leaving air temperature of the fan coil. The temperature

information is for display purposes only. The system does not react
to this temperature reading.

Indoor Coil Temp:
This sensor is NOT required.

However, if HPT sensor is

connected to the Damper Control Module, the sensor will read
temperature at that location (i.e. if placed down stream from

evaporator coil, and before electric heat, will read coil leaving air
temperature). The temperature information is for display purposes

only. The system does not react to this temperature reading.

Blower RPM:

S

Actual blower motor RPM value

Static Press:

S

Inches of water. Displays the calculated static pressure
the fan coil is currently experiencing.

S

If static pressure cannot be accurately calculated, the dis-
play will read UNKNOWN. When this is seen, the sys-
tem is adjusting to high static pressure by cutting back

blower RPM.

Service -- Heat Pump / AC Status

Stage: (Heat / Cool)

S

OFF, LOW, HIGH

Displays stage of heating or cooling that the Heat Pump/AC is

delivering.

Defrost:

S

NO, YES

Displays status of defrost mode if heat pump.

Airflow CFM:

S

Airflow User Interface is requesting from blower.

Leaving Air Temp:
This sensor is NOT required

. However, if LAT sensor is

connected to the Damper Control Module, sensor will read leaving

air temperature of the indoor unit. The temperature information is

for display purposes only. The system does not react to this
temperature reading.

Outdoor Coil Temp:

S

_

F or

_

C (default =

_

F)

Temperature of the outdoor unit coil (only available on
communicating outdoor units).

Blower RPM:

S

Actual RPM feedback from indoor motor.

Static Press:

S

Calculated static pressure of indoor unit.

S

If static pressure cannot be accurately calculated, the dis-

play will read UNKNOWN. When this is seen, the sys-
tem is adjusting to high static pressure by cutting back

blower RPM.

Service -- Zoning Status

Zone Status:

This screen will show each zone in the system with the
corresponding damper position (POS), and CFM being delivered

to each zone. Damper position range is from 0 to 15 (0 = closed, 15
= open).

Service -- Last 10 System Events

 

LAST 10 EVENTS

LOW PRESSURE

3/2/05

2:35 PM

< BACK

MORE >

HP

3 EVENTS:

    225  EVENTS                     _

ACTIVE

FN  2/28/05  6:10 PM
41-BLOWER MOTOR FAULT

F

SWITCH OPEN

F=FAULT

A07032

Fig. 35 -- Last 10 System Events

This screen will show last 10 events that occurred throughout the

system. Each entry has the time and date incident recorded. Service

technician should enter current date in “

TODAY’S DATE

”menu

section BEFORE checking and logging the last 10 system events.

These events are stored in the memory of the User Interface and are
resettable in the Thermostat Setup screen under the Reset Factory

Default selection.
Each entry has a two--letter acronym preceding the event name to

identify which piece of equipment generated the event. This event

history can be cleared under Thermostat Setup, Reset Factory
Defaults.
HP = Heat Pump
AC = Air Conditioner
FN = Furnace
FC = Fan Coil
ZN1 = Zone Board 1
ZN2 = Zone Board 2
SPP = Packaged product
SAM = System Access Module

Service -- Run / Fault History

This information is stored in the equipment circuit boards (if
communicating) and displayed on the User Interface. The indoor

unit and outdoor unit (if communicating) have the following
histories:

NOTE

: For Critical Fault Screens, see Troubleshooting section in

this document.

Resettable Faults:

S

Fault counters for each piece of equipment that can be
reset.

Cycle Counters:

S

Number of heat/cool/power cycles the unit has per-

formed.

BBU

IZ

01

--

B

Содержание EVOLUTION Zone Control SYSTXBBUIZ01-B

Страница 1: ...all local electrical codes during installation All wiring must conform to local and national electrical codes Improper wiring or installation may damage the Evolution Zone System Recognize safety info...

Страница 2: ...indoor unit outdoor unit and accessories accord ing to their instructions S Wire complete system according to this instruction S Setup commission and operate system according to this instruction to as...

Страница 3: ...the elements The Damper Control Module and zone dampers may be installed in any area where the temperature remains between 4_F to 158_F 20_C to 70_C and there is no condensation The cover must be inst...

Страница 4: ...essed Mount Interlocking Tabs 4 Recessed terminal block in wall 11 2 38 1 mm wide by 21 8 54 mm high A07150 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4 A03191 Fig...

Страница 5: ...CAL OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation Improper wiring of the ABCD connector will cause the Evolution Zone System to operate improperl...

Страница 6: ...olation relay coil to furnace or fan coil HUM and COM terminals will allow the Evolution Zone Control to automatically energize the HUM output during a call for humidification The N O relay contacts w...

Страница 7: ...AC and the electric heater is not self identifying ELECTRIC HEATER NOT IDENTIFIED will appear See Fig 18 Press either Time or Temp buttons to select appropriate size of electric heater installed then...

Страница 8: ...Press right side button to start Duct Assessment Duct Assessment will measure the relative size of the ductwork up to and through the dampers These measurements are used to control the correct amount...

Страница 9: ...one schedule to other zones us ing NO or YES 11 Exit the scheduling mode by either closing the door or pressing the SCHEDULE button 12 If changes are made you will be asked to SAVE CHANGES YES NO INST...

Страница 10: ...ll settings in Install Service menus to factory default settings Last 10 System Events S Yes No to reset last 10 system events under Service Info menu Setup Furnace Upon a first time start up of the E...

Страница 11: ...midify mode is increased to reduce duct and register sweating Also increases minimum airflow during normal cooling opera tion to reduce duct sweating Heater Size S choices dependent upon fan coil mode...

Страница 12: ...er run time Airflow Limits Since bypass damper is prohibited in this system this setting is used to select the maximum allowable noise airflow relationship into each zone based on air noise and comfor...

Страница 13: ...e if the AC heat pump is a 2 stage model runs low speed only CHECKOUT MENUS CHECKOUT FURNACE HEAT PUMP HEATING HEAT PUMP COOLING HUMIDIFIER VENTILATOR BACK SELECT A03204 Fig 33 Checkout Menu The Check...

Страница 14: ...MEDIUM S HIGH default S MAXIMUM Because there is no bypass damper the Zone Airflow Limit check will allow the installer to assess the airflow noise generated by the system providing the maximum amoun...

Страница 15: ...er Control Module sensor will read leaving air temperature of the indoor unit The temperature information is for display purposes only The system does not react to this temperature reading Outdoor Coi...

Страница 16: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Страница 17: ...a Equipment stage down or shut off if necessary b Fault history will record an event of AIRFLOW LIM ITED STAGEDOWN OCCURRED on stagedown and EXCESS STATIC PRESSURE if shut down c If shut down occurs o...

Страница 18: ...e a mistake on the start up screens and hit the right side button to get to the run mode How do I get back to start up 1 Press the ADVANCED button for at least 10 seconds 2 Install Service menu will a...

Страница 19: ...r Fault cooling mode only ventilator humidifier dehumidifier outdoor unit will be turned off Code 45 Control Circuitry Lockout NOTE For codes 13 14 and 21 the system will use heat pump heating exclusi...

Страница 20: ...nge at any time specifications or designs without notice and without incurring obligations E2007 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in China Edition Date 03...

Отзывы: