The heat pump cooling mode (or AC cooling mode) can be
exercised with this menu option. With a 2--stage heat pump or AC

unit, a low cool runtime and a high cool runtime are independently
selectable to exercise. The display will change to show the heat

pump or AC operating status.
Default time = Fixed 5 min. minimum, range = 5 -- 120 min.

NOTE

:

Airflows during Checkout modes are fixed to the

Efficiency setting and are independent of other airflow settings. To
view airflows for normal heat pump heating mode, exit the
Checkout screen and apply a heating demand to the system.

Checkout -- Humidifier

S

OFF

S

ON

The humidifier can be exercised On and Off with this menu option.

Checkout -- Ventilator

Speed:

S

OFF

S

LOW

S

HIGH

The ventilator can be exercised through all of its operating speeds

with this menu option.

Checkout -- Zoning

Duct Assessment

This is the same Duct Assessment that runs on first start--up.
Measures duct capacity for each zone. The Duct Assessment will

perform an airflow measurement on each zone and determine the
relative size of each zone along with damper leakage. This

assessment will require approximately 1 minute for each zone in

the system.

NOTE

: A Duct Assessment will automatically occur every 24

hours at selected time to check system static and calibrate dampers.

Sensor / Damper Check:

The Sensor/Damper Check allows the installer to check each zone

damper for operation, as well as insure the zone sensor corresponds
to that particular zone.
When first initiated, the Zone 1 damper will fully open, and all

other zones will close. Using the scroll button, the installer can
select each zone and verify the damper is fully open while all other

dampers remain closed.
After proper damper operation has been verified, the installer can

now check and verify that each Remote Room Sensor corresponds
to the proper zone damper in the same zone. Start from the top and

highlight zone 1 to open damper. Temporarily disconnect any other

zone Remote Room Sensor (at sensor location). That zone damper
will now open, while the Zone 1 damper will close.
EXAMPLE: If the Zone 2 Remote Room Sensor is disconnected,
the Zone 2 damper will now open as indicated on the User

Interface display. The word

“FAIL”

will also be displayed instead

of the actual temperature for Zone 2. Reconnect Zone 2 sensor and
try all remaining sensors one at a time in the system. Smart Sensors

may also be checked, see Smart Sensor Installation Instructions for
procedure.

Airflow Limits:

S

LOW

S

MEDIUM

S

HIGH(default)

S

MAXIMUM

Because there is no bypass damper, the Zone Airflow Limit check

will allow the installer to assess the airflow noise generated by the
system providing the maximum amount of airflow to each zone.

Select ZONE, then select AIRFLOW LIMIT: Low, Medium, High
(default), or Maximum. When Start is pressed (right side button),

the selected zone’s damper will fully open, all others will close, and

the indoor unit will provide the maximum airflow for that zone (as
selected in SETUP — ZONING, Airflow Limits). If the airflow

noise is objectionable, the installer can select a lower airflow noise
limit. If the noise is not objectionable, the installer should leave

High selected, or even Maximum.

NOTE

: Selecting a lower airflow noise limit may decrease the

homeowner’s comfort in that zone.

Sensor Types:

Shows list of all zones with corresponding sensor types.
UI = User Interface
SS = Smart Sensor
RS = Remote Sensor

Checkout -- System Access Module (SAM)

See System Access Module Installation Instructions for full details.

SERVICE MENUS

The Service Info menu will only show the equipment installed in

the system. Below is a sample using a furnace and a heat pump

(Hybrid Heat). A sample service menu is shown in Fig. 34.

SERVICE INFO

FURNACE STATUS

HEAT PUMP STATUS

LAST 10 SYSTEM FAULTS

RUN/FAULT HISTORY

TODAY’S DATE

MODEL/SERIAL NUMBER

SERVICE PHONE NUMBER

   BACK               SELECT

A03205

Fig. 34 -- Service Menu

Service -- Furnace Status or Gas PAC Status

The Status screens will show all of the current operating parameters
of each installed piece of equipment.

NOTE

: To view a less detailed Equipment Status screen, press and

hold the right side button for 3 seconds. This will display
equipment stage, fan status, actual and target humidify settings.

Heat Stage:

S

OFF, LOW, HIGH

Displays stage of heat that the furnace is currently delivering.

Airflow CFM:

S

(furnace model dependent)

Cubic Feet per Minute of air the User Interface is currently
requesting.

Leaving Air Temp:
This sensor is NOT required

. However, if LAT sensor is

connected to the Damper Control Module, the sensor will read

leaving air temperature of the furnace. The temperature information
is for display purposes only. The system does not react to this

temperature reading.

Indoor Coil Temp:
This sensor is NOT required

. However, if HPT sensor is

connected to the Damper Control Module, the sensor will read

temperature at that location (i.e. if placed in return--air, will read
return--air temperature). The temperature information is for display

purposes only. The system does not react to this temperature

reading.

Inducer RPM (90% furnaces only):

S

Actual inducer motor RPM value.

Blower RPM:

S

Actual blower motor RPM value.

BBU

IZ

01

--

B

Содержание EVOLUTION Zone Control SYSTXBBUIZ01-B

Страница 1: ...all local electrical codes during installation All wiring must conform to local and national electrical codes Improper wiring or installation may damage the Evolution Zone System Recognize safety info...

Страница 2: ...indoor unit outdoor unit and accessories accord ing to their instructions S Wire complete system according to this instruction S Setup commission and operate system according to this instruction to as...

Страница 3: ...the elements The Damper Control Module and zone dampers may be installed in any area where the temperature remains between 4_F to 158_F 20_C to 70_C and there is no condensation The cover must be inst...

Страница 4: ...essed Mount Interlocking Tabs 4 Recessed terminal block in wall 11 2 38 1 mm wide by 21 8 54 mm high A07150 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4 A03191 Fig...

Страница 5: ...CAL OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation Improper wiring of the ABCD connector will cause the Evolution Zone System to operate improperl...

Страница 6: ...olation relay coil to furnace or fan coil HUM and COM terminals will allow the Evolution Zone Control to automatically energize the HUM output during a call for humidification The N O relay contacts w...

Страница 7: ...AC and the electric heater is not self identifying ELECTRIC HEATER NOT IDENTIFIED will appear See Fig 18 Press either Time or Temp buttons to select appropriate size of electric heater installed then...

Страница 8: ...Press right side button to start Duct Assessment Duct Assessment will measure the relative size of the ductwork up to and through the dampers These measurements are used to control the correct amount...

Страница 9: ...one schedule to other zones us ing NO or YES 11 Exit the scheduling mode by either closing the door or pressing the SCHEDULE button 12 If changes are made you will be asked to SAVE CHANGES YES NO INST...

Страница 10: ...ll settings in Install Service menus to factory default settings Last 10 System Events S Yes No to reset last 10 system events under Service Info menu Setup Furnace Upon a first time start up of the E...

Страница 11: ...midify mode is increased to reduce duct and register sweating Also increases minimum airflow during normal cooling opera tion to reduce duct sweating Heater Size S choices dependent upon fan coil mode...

Страница 12: ...er run time Airflow Limits Since bypass damper is prohibited in this system this setting is used to select the maximum allowable noise airflow relationship into each zone based on air noise and comfor...

Страница 13: ...e if the AC heat pump is a 2 stage model runs low speed only CHECKOUT MENUS CHECKOUT FURNACE HEAT PUMP HEATING HEAT PUMP COOLING HUMIDIFIER VENTILATOR BACK SELECT A03204 Fig 33 Checkout Menu The Check...

Страница 14: ...MEDIUM S HIGH default S MAXIMUM Because there is no bypass damper the Zone Airflow Limit check will allow the installer to assess the airflow noise generated by the system providing the maximum amoun...

Страница 15: ...er Control Module sensor will read leaving air temperature of the indoor unit The temperature information is for display purposes only The system does not react to this temperature reading Outdoor Coi...

Страница 16: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Страница 17: ...a Equipment stage down or shut off if necessary b Fault history will record an event of AIRFLOW LIM ITED STAGEDOWN OCCURRED on stagedown and EXCESS STATIC PRESSURE if shut down c If shut down occurs o...

Страница 18: ...e a mistake on the start up screens and hit the right side button to get to the run mode How do I get back to start up 1 Press the ADVANCED button for at least 10 seconds 2 Install Service menu will a...

Страница 19: ...r Fault cooling mode only ventilator humidifier dehumidifier outdoor unit will be turned off Code 45 Control Circuitry Lockout NOTE For codes 13 14 and 21 the system will use heat pump heating exclusi...

Страница 20: ...nge at any time specifications or designs without notice and without incurring obligations E2007 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in China Edition Date 03...

Отзывы: