background image

16

Run Times:

S

Lifetime hours of operation in heating, cooling, and how
long the unit has been powered.

Service -- Today’s Date

This menu item allows the installer to enter the current date. It is

used for time/date stamping of system faults. This should be
entered every time prior to viewing “LAST 10 SYSTEM

EVENTS” section.

Service -- Model / Serial Numbers

This menu item allows the installer to view the model number and
serial number (if available) of all communicating pieces of

equipment in the system. This information resides in the original
circuit board from the factory. If a circuit board has been replaced,

the model and serial number will no longer be displayed.

Service -- Service Phone Number

This menu item allows the installer to enter a name and phone
number that the homeowner can call for future service of the

system. This name and phone number will appear to the

homeowner whenever a service reminder pop--up message is
displayed (i.e. Change Filter, etc.)
To edit:

S

Use Temp +/-- button to move cursor left and right.

S

Use Time +/-- button to select numbers and letters.

S

Use Scroll button to move up and down between NAME

and NUMBER.

OPERATIONAL INFORMATION

Zone Selection

S

Press top left ZONE button to select zones.

Continuous Fan Operation

Pressing FAN button will scroll through the following:

S

AUTO = No fan operation except during equipment op-

eration.

S

LOW = Approximately 50% of High Speed operation.

S

MED = Half way between High and Low speed opera-

tion.

S

HIGH = Highest of either High Heating or High Cooling

CFM.

Continuous fan operation is programmable. The programming

option must be enabled in the Thermostat Setup. See the
Homeowner’s Manual for detailed instructions on programming

the fan.

Five--Minute Compressor Timeguard

This timer prevents compressor from starting unless it has been off
for at least 5 minutes. It can be defeated by simultaneously pressing

the Fan and Temp + buttons.

Emergency Heat (for heat pump applications)

To activate Emergency Heat, you must press and hold the HEAT
button for 3 seconds to activate. Repeat to deactivate.

Heat Source Selection (Hybrid or Hydronic Heat)

If user wishes to override normal operation in Hybrid Heat or
Hydronic Heat applications, press and hold the heat button for 3

seconds to select desired heat source.

Keypad Lockout

Keypad can be locked by pressing “Fan” and “Humidity/Oat”
buttons at the same time for 3 seconds. When keys are locked, a

lock symbol will appear in the upper left corner of screen. Follow

same procedure to unlock keypad.

Heat and Cool LED

The Heat and Cool LEDs will pulsate during actual equipment

operation. This can be defeated in the Advanced Setup Screens.

Equipment Cycle Timer (adjustable 4--6 cycles per

hour)

This timer prevents the start of a heating or cooling cycle until 15

(or 10) minutes after the last start of the same cycle. Its function is
to assure that the equipment is not cycled more than the selected

times per hour. This timer is adjustable from 4 to 6 cycles per hour.
This timer is defeated for one cycle when the desired temperature is

manually changed. It can also be defeated for one cycle by

simultaneously pressing the Fan and Temp + buttons.

Staging Timer

In multistage heating or cooling, this timer prevents any higher

stage from turning on until the preceding stage has been on for 10

minutes.
In Hybrid Heat, the staging timer is 15 minutes between heat pump

and gas furnace operation. A demand of 5

_

F / 2.8

_

C or more will

override the staging timer and allow higher stages to energize.

Three--Minute Minimum On Time

In normal operation, when a stage turns on, it will remain on for a

minimum of three minutes. If the setpoint is changed, this timer is
automatically cancelled, allowing the equipment to turn off

immediately when the demand is removed.

Heat/Cool Setpoints (Desired Temperatures)

A minimum difference of 2

_

F / 1.1

_

C (default) is enforced

between heating and cooling desired temperatures. This is done by

allowing one setting to “push” the other to maintain this difference.
This difference is adjustable via the Install/Service menu under

Thermostat Setup.

Temperature Display

The actual temperature displayed is always rounded toward the
setpoint. This is because the system is operating and measuring the

temperature in sixteenths of a degree, but displaying in whole

numbers. The system may be turned off and on within .5

_

F / .3

_

C

of setpoint, but the display may not change. This is by design and

does not indicate a problem with the control.

Auto Changeover

When Auto mode is enabled (factory default) a change from heat

to cool (or vice versa) will not occur until an opposite mode

demand has existed for 30 minutes. If the setpoint is changed, the
30--minute requirement is defeated. This Auto Changeover time is

adjustable via the Install/Service menu under Thermostat Setup.
Range = 5 -- 120 min.

Smart Recovery

With Smart Recovery selected (factory default), transition out of

setback begins 1.5 hours before selected recovery time and
gradually adjusts room temperature so desired temperature will be

achieved at selected recovery time. It operates in both heating and

cooling. This only applies to programmable operation.
For example: Set back temperature in heating is 64

_

F. Smart

Recovery setpoint is 70

_

F at 7:00 a.m. At 5:30 a.m., the control

calculates the required temperature recovery rate (recovery temp --

set back temp or current temp if greater) / 90 minutes. If the current

temp at 5:30 = 66

_

F, the recovery rate = (70 -- 66)

_

F/90 minutes =

0.04

_

per minute. In order to achieve setpoint, the control ramps up

the setpoint 0.04

_

F / minute from 5:30 a.m. until 7:00 a.m.

NOTE

: Temperatures should not be set back so far that the

equipment cannot recover in 90 minutes.

Media Filter

If

MEDIA

or

MEDIA+EAC

is installed in the indoor unit, the

system will perform a static pressure check of the system every 24
hours at 1:00 p.m. to monitor filter accumulation (TrueSense

t

Dirty Filter Detection) or whenever power is applied to the system
or the system is transitioned from Off to Cool or Heat modes. The

blower will run at a medium airflow for one minute.

BBU

IZ

01

--

B

Содержание EVOLUTION Zone Control SYSTXBBUIZ01-B

Страница 1: ...all local electrical codes during installation All wiring must conform to local and national electrical codes Improper wiring or installation may damage the Evolution Zone System Recognize safety info...

Страница 2: ...indoor unit outdoor unit and accessories accord ing to their instructions S Wire complete system according to this instruction S Setup commission and operate system according to this instruction to as...

Страница 3: ...the elements The Damper Control Module and zone dampers may be installed in any area where the temperature remains between 4_F to 158_F 20_C to 70_C and there is no condensation The cover must be inst...

Страница 4: ...essed Mount Interlocking Tabs 4 Recessed terminal block in wall 11 2 38 1 mm wide by 21 8 54 mm high A07150 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4 A03191 Fig...

Страница 5: ...CAL OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation Improper wiring of the ABCD connector will cause the Evolution Zone System to operate improperl...

Страница 6: ...olation relay coil to furnace or fan coil HUM and COM terminals will allow the Evolution Zone Control to automatically energize the HUM output during a call for humidification The N O relay contacts w...

Страница 7: ...AC and the electric heater is not self identifying ELECTRIC HEATER NOT IDENTIFIED will appear See Fig 18 Press either Time or Temp buttons to select appropriate size of electric heater installed then...

Страница 8: ...Press right side button to start Duct Assessment Duct Assessment will measure the relative size of the ductwork up to and through the dampers These measurements are used to control the correct amount...

Страница 9: ...one schedule to other zones us ing NO or YES 11 Exit the scheduling mode by either closing the door or pressing the SCHEDULE button 12 If changes are made you will be asked to SAVE CHANGES YES NO INST...

Страница 10: ...ll settings in Install Service menus to factory default settings Last 10 System Events S Yes No to reset last 10 system events under Service Info menu Setup Furnace Upon a first time start up of the E...

Страница 11: ...midify mode is increased to reduce duct and register sweating Also increases minimum airflow during normal cooling opera tion to reduce duct sweating Heater Size S choices dependent upon fan coil mode...

Страница 12: ...er run time Airflow Limits Since bypass damper is prohibited in this system this setting is used to select the maximum allowable noise airflow relationship into each zone based on air noise and comfor...

Страница 13: ...e if the AC heat pump is a 2 stage model runs low speed only CHECKOUT MENUS CHECKOUT FURNACE HEAT PUMP HEATING HEAT PUMP COOLING HUMIDIFIER VENTILATOR BACK SELECT A03204 Fig 33 Checkout Menu The Check...

Страница 14: ...MEDIUM S HIGH default S MAXIMUM Because there is no bypass damper the Zone Airflow Limit check will allow the installer to assess the airflow noise generated by the system providing the maximum amoun...

Страница 15: ...er Control Module sensor will read leaving air temperature of the indoor unit The temperature information is for display purposes only The system does not react to this temperature reading Outdoor Coi...

Страница 16: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Страница 17: ...a Equipment stage down or shut off if necessary b Fault history will record an event of AIRFLOW LIM ITED STAGEDOWN OCCURRED on stagedown and EXCESS STATIC PRESSURE if shut down c If shut down occurs o...

Страница 18: ...e a mistake on the start up screens and hit the right side button to get to the run mode How do I get back to start up 1 Press the ADVANCED button for at least 10 seconds 2 Install Service menu will a...

Страница 19: ...r Fault cooling mode only ventilator humidifier dehumidifier outdoor unit will be turned off Code 45 Control Circuitry Lockout NOTE For codes 13 14 and 21 the system will use heat pump heating exclusi...

Страница 20: ...nge at any time specifications or designs without notice and without incurring obligations E2007 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in China Edition Date 03...

Отзывы: