6.3.10.
Utility Curtailment
NOTE
: Utility Curtailment and Utility Saver functions are different than the Utility
Demand Response function described in the Owner’s Manual. Utility
Curtailment/Utility Saver uses the UTIL and Y2 (or equivalent) terminals on the
Evolution System compressor section control board to receive a dry contact relay
signal from the Utility, typically from the electric meter assembly, to signal a
curtailment period. This section describes the actions taken in response to that
signal. See the equipment installation instructions for more information on wiring
the compressor section control board to the Utility connections.
Utility Saver is used to force the equipment to a lower stage (low or off) when
activated by the utility company, typically during peak load times. This setup is
available only if the equipment has a utility saver input (refer to outdoor equipment
installation instructions). This setup controls the response of the equipment when
the utility saver input is active.
DISABLED
means that the curtailment function is
not active.
TURN OFF
means the outdoor unit is to be turned off when the
curtailment function is active.
LOW STAGE
means the outdoor unit will run in
lows stage when the curtailment function is active. After the selections are made,
touch
SAVE
.
A12193
Содержание Evolution Connex Control
Страница 108: ...99 A160170 NIM Chart...
Страница 109: ...100 A160171 Wiring Diagram Single Stage Non Communicating Heat Pump NIM...
Страница 110: ...101 A160172 Wiring Diagram Two Stage Non Communicating Heat Pump NIM...
Страница 111: ...102 R G FE Fan Coil or Variable Speed Furnace A07114 G Input Wiring for Blower Operation...
Страница 112: ...103 R G FE Fan Coil or Variable Speed Furnace A07115 G Input Wiring for System Shutdown...
Страница 115: ...106 NOTES...