56
6.3.7.3. Brownout Override
This option controls the low voltage brownout override function in the Geo HP unit.
After the selection is made, touch
SAVE
.
S
Brownout Override:
Active or Inactive
d
Default = Inactive
A150181
6.3.7.4. Geothermal HP Energy Tracking
Energy tracking for geothermal heat pumps requires the installation of an Entering
Water Temperature (EWT) sensor. See the geothermal heat pump literature for
information on installing this sensor.
If the EWT sensor is installed, the installer will be able to enter the Loop Flow Rate
and the Loop Pump power. See the figure in Section 6.3.7. These inputs will help
the Energy Tracking algorithm properly calculate geothermal heat pump usage. See
the geothermal heat pump literature for details.
If the EWT error message is shown, as illustrated in Section 6.3.7, that means that
the EWT sensor was installed and had valid readings at one time, but is now
malfunctioning. See the geothermal heat pump literature for details.
Содержание Evolution Connex Control
Страница 108: ...99 A160170 NIM Chart...
Страница 109: ...100 A160171 Wiring Diagram Single Stage Non Communicating Heat Pump NIM...
Страница 110: ...101 A160172 Wiring Diagram Two Stage Non Communicating Heat Pump NIM...
Страница 111: ...102 R G FE Fan Coil or Variable Speed Furnace A07114 G Input Wiring for Blower Operation...
Страница 112: ...103 R G FE Fan Coil or Variable Speed Furnace A07115 G Input Wiring for System Shutdown...
Страница 115: ...106 NOTES...