9
Sensor 1
Sensor 2
Sensor 3
Sensor 4
Damper Control
Module
ZS_
Damper Control
Module
ZS_C
A03233
4.3.3.
Smart Sensors (for zoning applications)
Any zone may use a Smart Zone Sensor (SYSTXBBSMS01). It provides a
temperature display and buttons to adjust the desired temperature in that zone only.
It also displays outdoor temperature and indoor humidity sensed at the Zone 1
Evolution Connex Control. Only one Smart Sensor may be used per zone. They
cannot be averaged like Remote Room Sensors. If a Smart Sensor is used in a zone,
one wired Remote Room Sensor may also be used in the same zone. The wired
Remote Room Sensor has priority over the Smart Sensor; the Smart Sensor will
display the wired Remote Room Sensor temperature, when used.
NOTE
: Smart Sensors must be addressed to identify which zone it will control. See
Smart Sensor Installation Instructions for details.
4.4.
Wiring Considerations
Ordinary thermostat wire is recommended. See Section 4.4.1 for notes on shielded
wire. Continuous wire lengths over 25 ft. should use 18 AWG wiring.