36
6.3.2.
Fan Coil
First touch
SETUP
, then touch
FAN COIL
to set up the parameters for the fan coil
unit.
A14223
6.3.2.1.
Airflow
This option allows the installer to select the appropriate air flow based on the needs
of the installation. The
QUIET
airflow means the minimum cooling airflow that the
system can safely run (typically 300 CFM/ton). Use this setting if duct noise is a
severe problem. Note that duct sweating in high humidity environments could
become an issue at low airflows. The
COMFORT
airflow means airflow is varied
depending on humidity and temperature demand settings. This selection enables the
full dehumidify and comfort capabilities of the system. The
EFF325
airflow is a
fixed airflow used to achieve specified ratings – no dehumidification airflow
reduction is performed. This is nominally 325 CFM/ton, but will vary if a 2--stage
outdoor unit is used. The
EFF350
airflow is a fixed airflow used to achieve
specified ratings – no dehumidification airflow reduction is performed. This is
nominally 350 CFM/ton, but will vary if a 2--stage outdoor unit is used. The
MAX
airflow is a fixed 400 CFM/ton. No dehumidification airflow reduction is
performed.
Содержание Evolution Connex Control
Страница 108: ...99 A160170 NIM Chart...
Страница 109: ...100 A160171 Wiring Diagram Single Stage Non Communicating Heat Pump NIM...
Страница 110: ...101 A160172 Wiring Diagram Two Stage Non Communicating Heat Pump NIM...
Страница 111: ...102 R G FE Fan Coil or Variable Speed Furnace A07114 G Input Wiring for Blower Operation...
Страница 112: ...103 R G FE Fan Coil or Variable Speed Furnace A07115 G Input Wiring for System Shutdown...
Страница 115: ...106 NOTES...