38
function to run longer, greatly improving humidity control in cooling mode.
Accumulated electrical energy used while reheating (in kilowatt--hours) is shown
on the Fan Coil Run Hours screen and can be reset there. This option is only
available with fan coil systems. Self--identifying (staging) heaters provide the best
performance for re--heat dehumidification. For re--heat applications, 9kW heaters
provide the best performance. The reheat algorithm functions along with the
overcool algorithm. If the room temperature is low enough that overcooling is not
allowed, reheat will not be allowed. Overcooling must happen before the electric
heaters are energized.
After the selections are made, touch
SAVE
.
S
Dehum Drain Time:
Adjustable from 5 to 60 minutes or OFF
d
Default = 15 minutes
S
Electric Reheat:
Yes or No
d
Default = No
6.3.2.4.
G--Terminal Input
This setup option selects desired operation when the
R
to
G
contact is closed on the
fan coil control board. Under this function option,
fan
turns on fan to selected fan
speed when G terminal is energized. Use the
alert
function to select the contact
state for an alert. Select Normally Open or Normally Closed, and then save your
selection.
Shutdown
shuts off fan and equipment when initiated. After the
selections are made, touch
Save
.
S
Shutdown:
d
Normally Open
d
Normally Closed
Содержание Evolution Connex Control
Страница 108: ...99 A160170 NIM Chart...
Страница 109: ...100 A160171 Wiring Diagram Single Stage Non Communicating Heat Pump NIM...
Страница 110: ...101 A160172 Wiring Diagram Two Stage Non Communicating Heat Pump NIM...
Страница 111: ...102 R G FE Fan Coil or Variable Speed Furnace A07114 G Input Wiring for Blower Operation...
Страница 112: ...103 R G FE Fan Coil or Variable Speed Furnace A07115 G Input Wiring for System Shutdown...
Страница 115: ...106 NOTES...