32
6.3.1.2.
Heat/Cool Deadband
The minimum difference enforced between heating and cooling desired
temperatures. The deadband does not change when the user changes between
Fahrenheit (
_
F) and Celsius (
_
C). Ex: A 2
_
deadband will be 2
_
F or 2
_
C and does
not change with units,
_
F and
_
C. This can allow one setting to “push” the other to
maintain this difference. When the correct deadband is set, touch
SAVE
.
S
Deadband
: Adjustable from 0 to 6
_
d
Default = 2
_
6.3.1.3.
Offsets
This option allows calibration (or deliberate miscalibration) of the temperature and
humidity sensors. These offsets are added to the actual temperature/humidity
values. See also Section 6.3.8.2. When the correct offsets are made, touch
SAVE
. If
the system is non--zoned, the indoor temperature offset is found on this screen. If
the system is zoned, the indoor temperature offset is found in the Zoning, Offsets
screen.