![Brink Air Comfort Скачать руководство пользователя страница 47](http://html.mh-extra.com/html/brink/air-comfort/air-comfort_installation-regulations_2812493047.webp)
13 Setting values
13.1 Parameter list
Parameter
Description
Default
Setting range
Step
1
T_max - Max. discharge temperature
60
1.0°C – 70.0°C
0.5°C
2
Qv_min – Set. percentage min. flow rate
20
10% – 100%
1%
3
Qv_max – Set. percentage max. flow rate
65
10% – 100%
1%
4
Qv_cooling – Set. percentage flow rate
cooling
80
10% – 100%
1%
5
T_start - Start temperature control
30.0
0.0°C – 60.0°C
0.5°C
6
T_fan on - Ventilator switching on
temperature
30.0
0.0°C – 60.0°C
0.5°C
7
T_fan off - Ventilator switching off
temperature
25.0
0.0°C – 60.0°C
0.5°C
8
Hysteresis ventilator switching temperature
1.0
0.0°C – 5.0°C
0.1°C
9
Ventilation programme
0
(op pagina 14)
(op pagina 16)
(op pagina 17)
1
10
Frost protection limit 1
5.0
-20.0°C – +30.0°C
0.5°C
11
Frost protection limit 2
0
-20.0°C – +30.0°C
0.5°C
12
Hysteresis frost protection
2
0.0°C – 5.0°C
0.1°C
13
Switching eBus CO
2
sensors off and on
OFF
ON/OFF
---
14
Min. ppm eBus CO
2
sensor A
400
400 ppm – 2000 ppm
25
15
Max. ppm eBus CO
2
sensor A
1200
400 ppm – 2000 ppm
25
16
Min. ppm eBus CO
2
sensor B
400
400 ppm – 2000 ppm
25
17
Max. ppm eBus CO
2
sensor B
1200
400 ppm – 2000 ppm
25
18
Min. ppm eBus CO
2
sensor C
400
400 ppm – 2000 ppm
25
19
Max. ppm eBus CO
2
sensor C
1200
400 ppm – 2000 ppm
25
20
Min. ppm eBus CO
2
sensor D
400
400 ppm – 2000 ppm
25
21
Max. ppm eBus CO
2
sensor D
1200
400 ppm – 2000 ppm
25
22
Address CO
2
sensor A
5
5 – 30
1
23
Address CO
2
sensor B
6
5 – 30
1
24
Address CO
2
sensor C
7
5 – 30
1
25
Address CO
2
sensor D
8
5 – 30
1
26
Air Comfort index number
6
1 – 8
1
27
HRU index number
7
7 = Excellent 300
8 = Excellent 400
1
Air Comfort 614788-B
Brink / 47
Содержание Air Comfort
Страница 1: ...Air Comfort English Installation regulations ...
Страница 2: ......
Страница 13: ...Water connections left hand version Air Comfort Air Comfort 614788 B Brink 13 ...
Страница 50: ...614788 B ...