![Brink Air Comfort Скачать руководство пользователя страница 40](http://html.mh-extra.com/html/brink/air-comfort/air-comfort_installation-regulations_2812493040.webp)
11 Electrical connections
accessories
11.1 Connecting external connectors Air Comfort
1
2
3
4
5
6
7
8
9
1
2
1
2
1
2
1.
External contacts - These contacts are used to connect external devices onto the appliance.
▪
Position 1 and 2 - This is a switch contact for the cooling. The cooling is activated if contact is made.
▪
Position 3 and 4 - This is a switch contact for an external fault. The system ventilator of the appliance is
switched off in the event of a fault
E107
, see
▪
Position 5 and 6 - This relay is activated by the frost protection, for example through introducing an external
pump.
▪
Position 7 and 8 - This relay is activated by cooling, for example through connecting an interface for the
cooling.
2.
24V power - maximum 4.5 VA (black).
3.
eBus communication - the connection is polarity sensitive (green).
4.
eBus communication - the connection is polarity sensitive (green).
5.
Connection 4
‑
position switch.
Air Comfort 614788-B