4.3 CO
₂
-control
A maximum of 4 CO
2
sensors can be connected to the Air Comfort. These CO
2
sensors help to maintain the air
quality of the separate rooms to which the Air Comfort is connected.
The CO
2
sensors have a minimum and maximum setting value. If the CO
2
concentration in a room gets above the
minimum setting value, the air flow of the system ventilator of the Air Comfort increases. The air flow varies
depending on the measured CO
2
concentration(s). The air flow to be supplied is based on the room (CO
2
sensor)
with the highest CO
2
concentration.
Important
The CO
2
control only works if the 4-position switch is on position1 or if no 4-position switch is
connected.!
1.
Air flow [%]
2.
CO
2
[PPM]
3. Air flow-max [m
3
/h]
4. Air flow-min [m
3
/h]
5. Min CO
2
[PPM]
6. Max CO
2
[PPM]
When heating is required from the Air Comfort appliance with CO
2
sensors the air flow is determined by the air
discharge temperature or the CO
2
sensors. The one with the highest demand determines the regulation of the air
flow.
Air Comfort appliances with CO
2
-sensors
1. CO
2
-sensors (max. 4)
Air Comfort 614788-B
Brink / 19