![Brink Air Comfort Скачать руководство пользователя страница 15](http://html.mh-extra.com/html/brink/air-comfort/air-comfort_installation-regulations_2812493015.webp)
In the constant programme, the control of the system ventilator can be influenced by a 4-position switch.
▪
Position 1 - at temperatures below 30°C, the system ventilator always continues operating at the set minimum
air volume. At temperatures above 30°C, the air flow varies between the set minimum and the set maximum
air flow depending on the measured discharge temperature.
▪
Position 2 - the system ventilator is switched off if the discharge temperature falls below a set switching
temperature. If the temperature of the heat exchanger increases above this adjustable value, the system
ventilator is activated again. At temperatures above 30°C, the set minimum and the set maximum air flow
varies depending on the measured discharge temperature. The temperature for switching on and the
temperature for switching off, as well as the hysteresis of the switching temperatures for the ventilator can be
set with parameters
6
,
7
and
8.
1.
Air flow [m
3
/h]
2.
Temperature [°C]
3. Air flow-max [m
3
/h]
4. Air flow-min [m
3
/h]
5. Off
6. Temperature fan out [°C]
7. Temperature start [°C]
8. Temperature max. [°C]
▪
Position 3 - the system ventilator continues to operate at the set maximum air flow.
1.
Air flow [m
3
/h]
2.
Temperature [°C]
3. Air flow-max [m
3
/h]
4. Air flow-min [m
3
/h]
5. Temperature fan out [°C]
6. Temperature start [°C]
7. Temperature max. [°C]
▪
Position - the system ventilator continues to operate at the set air flow for cooling. The switch output for
cooling is closed. This position only works if the
(op pagina 20) is not active. The air flow for
the cooling can be set with parameter
4
.
1.
Air flow [m
3
/h]
2.
Temperature [°C]
3. Air flow-cooling [m
3
/h]
4. Air flow-max [m
3
/h]
5. Air flow-min [m
3
/h]
6. Temperature fan out [°C]
7. Temperature start [°C]
8. Temperature max. [°C]
Air Comfort 614788-B