FPD-7024
|
Operation and Installation Guide | 5.0
Control Panel Programming
72
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
Press the number that corresponds with the device you are adding or press [0/Prog] if you are removing a
device. When the device type is selected, the following window appears:
POINT NUMBER
(009 - 255) 009
Enter the address of the point being added, and press [#/Enter]. The device type window appears again
allowing additional devices to be added. Eight points are added at once when the D7042 is added to the
control panel.
5.9.2 MUX
Program
Shortcut: 0-
PROG
,
9-
PROGRAM MUX,
2
-MUX PROGRAM
To add MUX devices to the system simultaneously while programming an address into the device itself, use
the MUX Program option. This programs a specified address into the device, and also sets the control panel
to use the device.
The D7042 is programmed using switches and cannot be added using the MUX Program feature.
Use MUX Edit instead.
All devices must be removed from MUX bus A before programming by removing power from the
system, disconnecting the wires to the field devices, and re-powering the system. Failure to
disconnect devices results in all devices on loop A being programmed to the new address.
All programming is performed on Bus A, including addresses 129 to 255 that can only be installed on Bus B
for operation. Be sure to connect devices with addresses 129 to 255 to Bus B, not to Bus A.
If no devices are connected on Bus A, the following window appears. Otherwise an error message appears.
PROGRAM MUX
1-
NORMAL
2-
FAST
Select normal programming to add one or two devices. Select fast programming to program larger quantities
of identical devices to sequential addresses.
Normal Programming
If normal programming is selected, the following menu appears allowing selection of the device type being
programmed:
DEVICE TYPE (__)
0-
NO DEVICE
2-
SINGLE INPUT
3-
I/O MODULE
4-
MUX SMOKE
5-
SMOKE W/FRZ
6-
DUAL INPUT
7-
OCTAL INPUT
Description..................... Model
0- NO DEVICE
2- SINGLE INPUT ........ D7044/M, D7045, FMM-7045,
D7052(Class A)
3- I/O MODULE ............ D7053
4- MUX SMOKE ........... D7050, D7050TH, D343
5- SMOKE W/FRZ ....... Not Used
6- DUAL INPUT ............ D7052(Class B)
7- OCTAL INPUT.......... D7042
Enter the number that corresponds with the device you are adding, or select 0 if you are removing a device.
When the device type is selected, the following window appears:
POINT NUMBER
(009 - 255) 009
Enter the address of the point being added, and press [#/Enter]. The display asks you to attach the device
being programmed to the terminals for MUX bus A (see the following window). You can simply hold the