FPD-7024
|
Operation and Installation Guide | 5.0
Control Panel Programming
.
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
71
5.8.3 Alternate 4/2 Codes
Shortcut: 0-
PROG
,
8-
HSTRY DEFLTS,
3
- ALT 4/2 DEVICES
You can set all of the programming for 4/2 codes to an alternative set of default reports, as described in
Appendix D
on page 93. To cause a complete control panel default, use the default EE option.
The following window appears:
SETTING EEPROM
TO DEFAULT...
When the operation is complete, the previous menu appears.
5.9 Program
MUX
Shortcut: 0-
PROG
,
9-
PROGRAM MUX
1.
Unprogrammed devices on the bus will not operate or be supervised
2.
This menu is accessible only when the D7039 Multiplex expander is installed.
3.
Do not install more than one device programmed to the same address on the bus. Doing so
can inhibit alarm reporting from both devices.
Intermittent trouble reports from a particular MUX point address can indicate that more than one
device was programmed to that address.
The following window appears:
PROGRAM MUX
1-
MUX EDIT
2-
MUX PROGRAM
3-
BUS TYPE
4-
AUTO PROGRAM
5.9.1 MUX
Edit
Shortcut: 0-
PROG
,
9-
PROGRAM MUX
1
- MUX EDIT
To add MUX devices to the system, use the MUX Edit option. Each device must have a unique address
programmed using the address switches.
The following window appears:
DEVICE TYPE (__)
0-
NO DEVICE
2-
SINGLE INPUT
3-
I/O MODULE
4-
MUX SMOKE
5-
SMOKE W/FRZ
6-
DUAL INPUT
7-
OCTAL INPUT
Description..................... Model
0- NO DEVICE
2- SINGLE INPUT ........ D7044/M, D7045, FMM-7045,
D7052(Class A)
3- I/O MODULE ............ D7053
4- MUX SMOKE ........... D7050, D7050TH, D343
5- SMOKE W/FRZ ....... Not Used
6- DUAL INPUT ............ D7052(Class B)
7- OCTAL INPUT.......... D7042