FPD-7024
|
Operation and Installation Guide | 5.0
Control Panel Programming
42
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
The following window appears:
PROGRAM PINS
1-
PROGRAMR PIN
2-
USER PINS
Press [1] for programmer PIN. The following window appears:
USER 0
ENTER PIN:____
Enter the PIN and press [#/Enter]. After you have programmed the programmer PIN, the previous window
appears.
Program User PINs
Shortcut: 0-
PROG
,
2-
SECURITY
,
1-
PINS
Up to 15 additional user codes (or up to 99 additional users when the D7039 is installed) can be programmed
to protect the system from unauthorized operation and allow a record to be kept of actions by individual
system users.
The following window appears:
PROGRAM PINS
1 - PROGRAMR PIN
2 - USER PINS
Press [2/
▲
] for user PINs. The following window appears:
OTHER PINS
USER (01-15)
Enter the user for whom you want to program a PIN and press [#/Enter]. Example: For User 5, press [5]. The
following window appears:
USER 5
ENTER PIN: _____
Enter the PIN and press [#/Enter]. After you have programmed the user PIN, the previous window appears.
5.2.2 Authority
Shortcut: 0-
PROG
,
2-
SECURITY
,
2-
AUTHORITY
This feature determines which system actions a user can perform. Refer to
Table 18.
Table 18: PIN Authority Levels.
PIN Authority Level
Allowed Operations
Maximum (1)
All control panel operations, including programming and disable.
Medium (2)
System test modes, fire drill, reset, silence, view history.
Minimum (3)
Silence, view history.
None (0)
None.
The following window appears:
AUTHORITY
USER (01 - 15)