FPD-7024
|
Operation and Installation Guide | 1.0
Overview
.
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
15
Table 8:
Compatible Devices (continued)
D7052 Mux Dual Input
Fire
Connects to the multiplex bus of the FPD-7024 and provides two supervised input zones
for connecting conventional normally-open inputs. The D7052 draws operating power from
the FPD-7024.
D7053 Mux I&O Module
Fire
Connects to the multiplex bus of the FPD-7024 and implements a supervised local loop,
and a Form C relay output. Up to 20 modules can be connected to each MUX bus. The
D7053 draws operating power from the FPD-7024.
D7050/TH Mux Smoke
Detector
The D7050/TH is a photo-electric smoke detector with a heat option. It connects to the
multiplex bus of the FPD-7024. The D7050 draws operating power from the
FPD-7024.
Table 9:
Address Restrictions for the D7042, D7052, and D7053
Install D7042 modules only at addresses:
9 17 25 33 41 49 57 65
73
81
89
97
105
113
121
129
137 145 153 161 169 177 185 193
201
209
217
225
233
241
Do not install D7052 and D7053 modules at these addresses
16
24
32
40
48
56
64
72
80 88 96 104 112 120 128 136
144
152
160
168
176
184
192
200
208 216 224 232 240 248 255