FPD-7024
|
Operation and Installation Guide | 5.0
Control Panel Programming
44
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
The display scrolls through the TIMERS options. Press [2] for AC FAIL DELAY. The following window
appears:
AC FAIL DELAY
1-
WAIT FOR DC
2-
ENTER TIME
The wait for DC function causes the AC fail report to be sent when the battery is 25% depleted, based on the
measured voltage of the battery. If you want to WAIT FOR DC (25 percent of capacity), press [1]. The existing
setting is displayed in parentheses on the first line, either “DC”, or the number of hours selected. After you
program the AC Fail Delay, the previous window appears.
To ENTER TIME press [2]. The following window appears:
AC FAIL DLY (___)
(00-24 HRS): ____*
* Refer to
Table 15
on page 32.
Enter the time and press [#/Enter]. The existing setting is shown in parentheses on the first line. After you
program the AC Fail Delay, the previous window appears.
When Wait For DC is the existing selection, the Enter Time menu displays DC as the time in
hours
.
Auto Silence
Shortcut: 0-
PROG
,
3-
PROG SYSTEM
,
2-
TIMERS
This feature silences the sounding of an alarm condition on selected NACs after a certain amount of time.
When you use Auto Silence, pressing [0/Prog] disables the feature and the only way to turn off an alarm is to
manually silence it. Entering between 5 and 99 minutes means that the alarm sounds for that much time
before automatically silencing.
If the condition is not corrected after an alarm is silenced (automatically or manually), the alarm
sounds again after 24 hours.
The system must eventually be reset after silencing to allow the alarmed zones to restore and
detect new alarms.
The display scrolls through the TIMERS options. Press [3] for AUTO SILENCE. The following window
appears:
AUTO SILENCE (__)
(0, 5-99 min): ____
Enter desired length of time (or press [0/Prog] to disable) and press [#/Enter]. The existing setting is shown in
parentheses on the first line. After you program the auto silence, the previous window appears.
Display Rate
Shortcut: 0-
PROG
,
3-
PROG SYSTEM
,
2-
TIMERS
Set the speed at which menus are displayed on the LCD (in units of 0.25 sec).