
FPD-7024
|
Operation and Installation Guide | 3.0
System Operation
28
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
M:
Missing device - the device cannot be found
on the loop. Unless a device was
programmed into the system (such as using
MUX EDIT), it is not considered missing.
T:
Tamper – the detector’s case was opened.
F:
Loop fault - the loop from a contact input
device is open, or the device is faulted.
A:
Loop alarm - the point is in alarm.
Pressing [*/Back] ends the display for any of these
modes.
Examples: X0L0R0D0M0T0F0A0 (relay off, not
dirty, not missing, no tamper, no fault and no alarm).
3.4.9 Sensitivity
Test
Tests the mux smoke detectors to determine if they
are within their normal range of sensitivity. Press
[Test] then [9].
3.5 Point/Zone
Mapping
The control panel supports a flexible system to map
input points to output points. The system defaults so
that all NAC outputs are activated by a fire alarm. By
programming output zones, you can create almost
any output activation scheme, such as “floor above
and floor below” activation or conditional elevator
recall.
Input points:
Smoke detectors, pull stations, and
so on.
Zone:
A group of input points (Zones 1 to
50 are configurable, 52 to 63 are
activated automatically).
Output points:
NACs (notification appliance
circuits) such as bells, strobes, and
relays.
Inputs activate zones, and zones activate outputs.
Zones 1 to 50 are available for the installer to
program. Each input can activate one zone;
however, any number of inputs can be mapped to
the same zone.
Zones above 50 are automatically activated by
inputs. For example, any input that is configured as
a waterflow type activates Zone 61 when it is
alarmed. Any output driven by Zone 61 activates
when any waterflow type point is alarmed.
Refer to
Figure 10
to show how inputs control zones
and zones control outputs.