FPD-7024
|
Operation and Installation Guide | 5.0
Control Panel Programming
48
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
Assigning Point Functions
Shortcut: 0-
PROG
,
4-
PROG INPUTS
,
1-
POINT NUMBER
This feature assigns each point to one point function. A point function is a set of characteristics that you can
assign to selected points. There are 16 point functions to choose from. Refer to
Section 4.2 Point
Programming
on page 33 for more information.
Refer to
Loop Response
on page 51 for the limitations when assigning points to point functions
that were programmed with a response time other than Fast.
Enter the point number you wish to program and press [#/Enter]. The display scrolls through the PROG
INPUT options.
Press [0/Prog] to select FUNCTION. The following window appears:
POINT FUNC. (___)
(01 - 16): ___
Enter the function number you wish to assign to the point and press [#/Enter]. The existing setting is shown in
parentheses on the first line. After you assign a point function, the previous window appears.
Alarm/Trouble Status
Shortcut: 0-
PROG
,
4-
PROG INPUTS
,
1-
POINT NUMBER
This feature allows you to program the system response to an open loop condition. A shorted loop always
causes an alarm condition. Refer to
Table 15
on page 32.
ALARM: A point in an open circuit state causes an alarm.
TROUBLE: If a point is in an open circuit state, the system responds with a trouble condition.
Enter the point number you wish to program and press [#/Enter]. The display scrolls through the PROG
INPUT options.
Press [1] to select ALARM/TROUBLE. The following window appears:
OPEN STATUS (__)
1-
ALARM
2-
TROUBLE
Press [1] to select ALARM on open loop and ALARM on shorted loop or [2] to select TROUBLE on open loop
and ALARM on shorted loop. The previous window appears. The existing setting is shown in parentheses on
the first line.
Output Zones
Shortcut: 0-
PROG
,
4-
PROG INPUTS
,
1-
POINT NUMBER
Enter the point number you wish to program and press [#/Enter]. The display scrolls through the PROG
INPUT options.
Press [2] to select OUTPUT ZONE. The following window appears:
OUTPUT ZONE ZZZ
(01 - 50): ___
Press the number key that corresponds to your selection.
ZZZ
indicates the point being programmed. The
existing setting is shown on the second line. After you set up the output zone, the previous window appears.