FPD-7024
|
Operation and Installation Guide | 5.0
Control Panel Programming
.
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
63
Tone
Shortcut: 0-
PROG
,
6-
PROG ACC’NTS
,
1-
PHONE/IP NUMS
The FREQ (_) programming items (refer to window below) modify the reporting format when 3/1 or 4/2 tone
burst reporting is selected for the format. Select three parameters with one setting: data tone frequency,
acknowledge tone frequency, and data rate. The frequency that the control panel uses to send data pulses
can be set for 1900 Hz (19D) or 1800 Hz (18D). The frequency of the acknowledge tone from the receiver to
which control panel responds can be set to 1400 Hz (14A) or 2300 Hz (23A). The rate at which the data
pulses are sent can be set to 10, 20, or 40 pulses per second (10PS, 20PS or 40PS).
The display scrolls through the Phone/IP Number options (refer to
Section 5.6.1 Phone Numbers/IP
Addresses
on page 58). Press [5] for TONE. The following window appears:
FREQ (__)
1-
19D, 14A, 10PS
2-
18D, 23A, 10PS
3-
19D, 14A, 20PS
4-
18D, 23A, 20PS
5-
19D, 14A, 40PS
6-
18D, 23A, 40PS
Press the number key that corresponds to your selection. The previous window appears.