FPD-7024
|
Operation and Installation Guide | 5.0
Control Panel Programming
.
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
51
ACTVTN TYPE (__)
1-
FIRE
2-
WATERFLOW
3-
SUPERVISORY
4-
(reserved)
5-
RESET
6-
SILENCE
7-
AC FAULT
Press the number key that corresponds to your selection. (The existing setting is shown in parentheses on
the first line.) The previous window appears.
Local Only
Shortcut: 0-
PROG
,
4-
PROG INPUTS
,
2-
POINT FUNCTION
Enabling this feature provides the input point for local annunciation only, with no communicator report.
Enter the point number you wish to program and press [#/Enter]. The display scrolls through the PROG
FUNCTION options.
Press [1] to select LOCAL ONLY. The following window appears:
LOCAL ONLY
____: YES (1)NO(0)
Press either [1] to enable or [0/Prog] to disable. The previous window appears.
Silencing
Shortcut: 0-
PROG
,
4-
PROG INPUTS
,
2-
POINT FUNCTION
This feature determines if a user may silence the system or not.
When an output is controlled by at least one zone activated by a Non-silencing point or a Non-
silencing zone (for example, zone 53), it becomes a Non-silencing output even if other silencing
zones activate it.
Enter the point number you wish to program and press [#/Enter]. The display scrolls through the PROG
FUNCTION options.
Press [3] to select SILENCEABLE. The following window appears:
SILENCABLE? (FF)
____: YES (1)NO(0)
Press either [1] to enable or [0/Prog] to disable. The previous window appears.
FF
indicates the function being programmed.
Loop Response
Shortcut: 0-
PROG
,
4-
PROG INPUTS
,
2-
POINT FUNCTION
This feature allows you to configure points to activate with standard response time (setting 1) or one system-
wide programmed response time (setting 2).
Enter the point number you wish to program and press [#/Enter]. The display scrolls through the PROG
FUNCTION options.
Press [4/ ] to select LOOP RESPONSE. The following window appears: