FPD-7024
|
Operation and Installation Guide | 5.0
Control Panel Programming
70
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
BFSK RPT CDS
1-
OFF NORM TEST
2-
OPEN/RESET
3-
SILENCE
4-
FIRE DRILL
5-
FR DRIL RSTR
Press the number key that corresponds to your report code selection. A window allowing entry of two hex
digits appears.
5.8 HISTORY
DEFAULTS
Shortcut: 0-
PROG
,
8-
HSTRY DEFLTS
The following window appears:
PROG DEFAULTS
1-
CLEAR HSTRY
2-
DEFAULT EE
3-
ALT 4/2 CDES
4-
(reserved)
5.8.1 Clear
History
Shortcut: 0-
PROG
,
8-
HSTRY DEFLTS,
1
- CLEAR HISTORY
You can use this option to clear some or all of the history records in the system.
The following window appears:
HIST ITEMS=____
DEL OLDEST 000
Enter the number of history records you wish to delete, and press [#/Enter]. The previous menu appears.
5.8.2 Default
EE
This option is only available from the local keypad.
Shortcut: 0-
PROG
,
8-
HSTRY DEFLTS,
2
- DEFAULT EE
You can set the control panel back to the original factory-programming configuration with this option. You are
asked to press [#/Enter] to complete the operation. Press [*/Back] to cancel the operation.
All programming, including zone configurations and option installations, are lost when this
operation is performed. You must turn control panel power off and on after resetting the default, to
reinstall the four zone expanders and the MUX expander. You must update the option bus and set
up keypads (PROG SYSTEM MENU) to reinstall option bus devices.
The following window appears:
SETTING EEPROM
TO DEFAULT...
When the operation is complete, the previous menu appears. This operation takes several minutes when the
D7039 Multiplex Expander is installed.