40
en | Planning Information
Analog fire panels
2017.11 | 2.0 | F.01U.173.607
Installation and Operation Guide
Bosch Security Systems, Inc.
Address
Device Description
Comment
37
PORT 1
NIC Port 1 Disconnect
38
PORT 2
NIC Port 2 Disconnect
39
PORT 3
NIC Port 3 Disconnect
46
Wiring
Open loop of topology
47
New Panel
New panel (according to panel list)
48
Panel Reused ID
Panel ID used more than once
49
Group Configuration
Group configuration conflict
50
Global Configuration
Global configuration conflict
51
Control
Control command conflict
52
Panel Missing
Missing panel (according to panel list)
53
OutofSync
indicates events on a panel or panels
are not fully synchronized with events
on another panel or panels
Tab. 3.24:
Mainboard address assignment
3.5
Reporting Requirements
Notice!
For UL Listed Fire Installations, shared on premises communications equipment must be UL
Listed for Information Technology Equipment.
The communicator can report to two phone numbers, two IP addresses, or one phone line and
one IP address with full, single, double, and back‑up reporting.
!
Caution!
When programming two accounts with different IP addresses, each account must be
programmed to a different port to prevent IP path and/or COMM fault trouble.
Possible DACT communication formats are:
–
SIA-DCS 300 no text
–
Modem IIIa
2
no text
–
Contact ID
–
SIA-DCS 300 with text
–
Modem IIIa
2
with text
Notice!
The communicator must be enabled and configured before it operates. The communicator
and phone line monitors are disabled in the default factory configuration.