Analog fire panels
Appendices | en
119
Bosch Security Systems, Inc.
Installation and Operation Guide
2017.11 | 2.0 | F.01U.173.607
Device Type
Programming Option
Default Setting
FAP-440-T
FAP-440-TC
FAP-440-DT
FAP-440-DTC
[SMOKE-M]
Zones
No zone assigned
Delay mode
No delay
Device LED flashing
Enabled (flashing wen polling)
Bypassed
Disabled
Point type
Fire automatic
Alarm mode
Multi-combined
Set point (Smoke)
2.50 %/ft (8.20 %/m)
Set point (Heat)
135°F (57°C)
RoR
Enabled
Label
[empty]
Day alarm mode
Multi-combined
Day sensitivity (Smoke)
2.50 %/ft (8.20 %/m)
Day sensitivity (Heat)
135°F (57°C)
RoR
Enabled
Smoke sensor (Multi-separated):
–
Smoke label
[empty]
–
Smoke point type
Generic
FAP-325-V2F
FAP-440
FAP-440-D
[SMOKE-P]
Zones
No zone assigned
Delay mode
No delay
Device LED flashing
Enabled (flashing when polling)
Point type
Fire automatic
Set point
2.50 %/ft (8.20 %/m)
Label
[empty]
Day sensitivity
2.50 %/ft (8.20 %/m)
Bypassed
Disabled
FAP-325
[SMOKE-P]
Zones
No zone assigned
Delay mode
No delay
Point type
Fire automatic
Set point
2.50 %/ft (8.20 %/m)
Label
[empty]
Day sensitivity
2.50 %/ft (8.20 %/m)
Bypassed
Disabled