Figure 3.3: Stand-alone panel zone mapping
For a list of all global zones on the panel (each has a unique number), see the following table.
Global Zone Number
Condition Activating Zone
226
Global fire alarm
227
Global trouble
228
Global supervisory
229
Alarm verification (verification period)
230
Pre-signal (waiting for reset)
231
Positive Alarm Sequence (waiting for ACK or reset)
232
Panel is resetting
233
Global gas alarm
234
Global waterflow
Tab. 3.18:
Pre-assigned zones
In some cases if a relay output is assigned to a certain global zone, other assigned zones are
ignored:
–
Mainboard relay 1: If assigned to the global alarm zone, other assigned zones are ignored.
The relay reacts only to the global alarm zone.
–
Mainboard relay 2: If assigned to the global trouble zone, other assigned zones are
ignored. The relay reacts only to the global trouble zone.
–
Mainboard relay 3: If assigned to the global supervisory zone, other assigned zones are
ignored. The relay reacts only to the global supervisory zone.
Outputs
is active if any zone to which the output is assigned is activated. An output which is assigned
to multiple zones can be considered as inactive only when all associated zones are inactive.