Analog fire panels
Installing | en
51
Bosch Security Systems, Inc.
Installation and Operation Guide
2017.11 | 2.0 | F.01U.173.607
Circuit Type
[Terminals]
Circuit Function
Power Rating / Wire Type / Limitations
SLC1
SLC2 (optional)
[S1+/SC1-/S2+/
SC2-]
Connects to
analog
addressable SLC
devices (as
specified in
Signaling Line
Circuit Devices,
page 17
)
Nominal 39 V DC (30 to 40 V DC), 260 mA per
FPE‑1000‑SLC
Plain wire, avoid twisted, shielded pair, maximum
line resistance 50 Ω (for maximum wiring distance,
see SLC wiring distances in
SLC module, page 61
)
City Tie (optional)
[ALM-/ALM+]
[SUP-/SUP+]
Connects to a
Master Box
(Local Energy) or
Central Station
(Reverse Polarity)
Reverse polarity or Local Energy: See
CITY TIE
module, page 59
Twisted, shielded pair or untwisted unshielded
pair, maximum line resistance 65 Ω
RELAY 1/2/3
[NO/C/NC]
Connects to
external devices
activated or
inactivated in
defined condition
30 V DC, 5 A / 120 V AC, 10 A
LINE 1/LINE 2
Connects to
PSTN (2 lines),
RJ45
Telephone cord such as the D162 Dual-modular
phone cord
ETHERNET
Connects to
Ethernet, RJ45
To connect a computer directly to the panel, use
cross-over or straight CAT 5 cable. The FPA-1000-V2
panel supports "auto crossover detection."
BATT
[-/+]
Connects to
backup batteries
2 x 12 V DC in series
12 AWG
2 x up to 18 Ah maximum (within enclosure)
or
2 x
up to 40 Ah maximum (external to enclosure)
Network Cards
Allows
connection for
panel network
Twisted pair (shielded or unshielded), maximum
length 2952 ft. (900 m)
or
CAT 5 cable or better,
maximum length 3280 ft. (1000 m)
or
Multi-mode
fiber optic cable with LC connector
62.5 µm/125 µm fiber size and 1300 nm (1270 nm
to 1380 nm) wavelength, maximum length 6560 ft.
(2000 m)
or
<10 dB loss
Tab. 4.30:
Overview of wiring requirements