Analog fire panels
Specifications | en
111
Bosch Security Systems, Inc.
Installation and Operation Guide
2017.11 | 2.0 | F.01U.173.607
8.3
Mechanical
Operating elements
Six LEDs
Fire, Gas Alarm, Power, Supervisory,
Silenced, and Trouble
Display
4-line x 20 character LCD display, backlit
Operation keys
Drill, Reset, Silence, and Acknowledge
Alphanumeric keypad
12 alphanumeric keys, escape, enter and
navigation buttons (left, right, up, down)
Interfaces
PSTN/DACT
2 lines, RJ45
Ethernet
1 x RJ45
Physical characteristics
Mounting holes
3, on back
Cable entries
Triple knockouts (1/2, 3/4, and 1 in.)
Connections
Pluggable terminal blocks for AUX, Option
Bus, SLC, NAC, Mainboard Relays, and City
Tie
Wire gauge
12 AWG to 18 AWG (ISO 4 mm
2
to 0.75 mm
2
)
Material
Cold rolled steel, 19 gauge (1.2 mm)
Color
Red
Dimensions (W x H x D)
14.5 in. X 4.3 in. x 22.7 in.
(36.8 cm x 10.9 cm x 57.7 cm)
Dimensions with trim ring (W x H x D)
Semi‑flush mounted (H recessed/H flush)
17.5 in. x 25.6 in x (44.5 cm x 65.0 cm)
3.25 in./1.05 in. (8.25 cm/2.7 cm)
Weight
Enclosure
18.1 lb. (8,2 kg)
Keypad with support
9.9 oz. (280 g)
Complete panel (with one FPE-1000-SLC and
FPE‑1000-CITY each, without batteries)
25.8 lb. (11.7 kg)
Gross weight (including packaging and
manuals, without batteries)
34.9 lb. (14.8 kg)
Notification appliance circuits (NACs)
Mainboard NACs
Two (NAC 1 and NAC 2)