Analog fire panels
System information | en
15
Bosch Security Systems, Inc.
Installation and Operation Guide
2017.11 | 2.0 | F.01U.173.607
Designation
Description
M34-75
Local energy Trip, Surface Mount, Cottage Shell (less inner case test block,
tap key & bell)
M34-92
Local energy Trip, Flush Mount, Gasketed cast frame for interior and exterior
use
M34-110
Same as M34-56 with plain door painted blue
M34-111
Same as M34-56 with plain door painted red
M34-112
Same as M34-56 with plain door painted yellow
M34-113
Same as M34-92 with plain door painted blue
M34-114
Same as M34-92 with plain door painted red
M34-115
Same as M34-75 with plain door painted blue
M34-116
Same as M34-75 with plain door painted red
Tab. 2.4:
Compatible Gamewell devices for the City Tie module in Local Energy mode
2.5
Power Supply
A transformer working with 120 V AC or 240 V AC is supplied standard with the control panel.
Two backup batteries with 7 Ah or 18 Ah each fit inside the fire panel cabinet. A separate
battery box can provide higher capacity.
Each FPA‑1000 provides two auxiliary power supplies: one 0.5 A at 24 V FWR; one 0.5 A
at 24 V DC RST (resettable). This auxiliary power can run expansion boards or other low
current auxiliary devices.
For a list of Bosch batteries and battery boxes, see the following table. For selecting the
necessary battery capacity, use the Microsoft Excel based
FPA‑1000_Battery_Calculator.xls
. The
spreadsheet can be downloaded at www.boschsecurity.com.
Type Number
Description
D126
Battery 12 V, 7 Ah
D1218
Battery 12 V, 18 Ah
D1224
Battery 12 V, 24 Ah
D1238
Battery 12 V, 38 Ah
BATB-40
Battery Box - provides a single level (two-battery capacity) of battery
storage with an optional shelf that increases the battery capacity to four
batteries.
BATB-80
Battery Box - Includes a mounted shelf that holds up to four batteries.
Tab. 2.5:
Bosch batteries and battery boxes
For installations requiring battery capacity higher than 40 Ah, a regulated and UL 1481 Listed
external power supply can be used. The external power supplies connect through the panel's
battery terminals. Batteries and battery charger are not supervised. For supervision of AC and
battery fault use an input module (for example FLM‑325‑2I4) on the SLC.