Analog fire panels
Installing | en
57
Bosch Security Systems, Inc.
Installation and Operation Guide
2017.11 | 2.0 | F.01U.173.607
Ground Wire Connections
When the mainboard is installed, connect the supplied ground wire between the door and the
enclosure using the supplied nuts (refer to Item 1 in the following figure). A second ground
wire is provided for connecting the ground to the dead front door (refer to Item 2 in the
following figure). Both grounds connect to the stud in the enclosure to the left of the
mainboard. Refer to the following figure.
1.
2.
Figure 4.7: Ground Wire Connections
4.7
Installing Optional Plug-in Modules
The mainboard allows for the installation of plug-in modules. The plug-in modules connect
directly to the mainboard. They are enabled by programming and supervised by the control
panel. See
Mounting plug-in modules, page 58
.
–
The first FPE-1000-SLC Signaling Line Circuit is mandatory equipment at the top position
on the mainboard
–
A second FPE-1000-SLC plug-in module can be installed as an option in the position
below the first SLC board
–
The position below that for the second SLC module can be equipped with an optional
FPE-1000-CITY Plug-in city tie module
–
An optional Networking Card can be installed along the bottom of the mainboard
To remove a plug-in module, press the snap-fit hook carefully from left to right and pull the
board toward the panel front.