16
en | System information
Analog fire panels
2017.11 | 2.0 | F.01U.173.607
Installation and Operation Guide
Bosch Security Systems, Inc.
2.6
Components Connected to the Option Bus
Remote Command Center and Annunciators
Each FPA-1000 panel supports up to:
–
a total of eight FMR-1000-RCMD and/or FMR-1000-RA LCD annunciators
–
eight D7030X Family annunciators with eight LED zones each
–
eight D7030X Family/D7032 combinations
For wiring requirements, see
Option Bus, page 67
. For address restrictions, see
Option Bus
Address Assignment, page 37
.
Type Number
Description
FMR-1000-RCMD LCD annunciator with control - remote operational terminal of the
FPA‑1000 panel, providing buttons for silence, reset, acknowledge, drill,
scrolling keys, key switch with 1358 key, built-in piezo sounder
FMR-1000-RA
LCD annunciator without control - remote LCD annunciator, providing key
for acknowledge and scrolling keys, built-in piezo sounder
D7030X
Annunciator, 8 alarm LED - identifies the location of a fire alarm for up to
eight zones allowed per system
D7030X-S2
Annunciator, 8 LED (2 supervisory) - with two zones reserved for
supervisory functions and with power and trouble LEDs plus eight-zone
LEDs that can be individually labeled
D7030X-S8
Annunciator, 8 LED (8 supervisory) - with eight zones reserved for
supervisory functions and with power and trouble LEDs plus eight-zone
LEDs that can be individually labeled
D7032
Annunciator expander, 8 LED - attaches to a D7030X, D7030X‑S2 or
D7030X‑S8 and identifies the location of a fire alarm for eight additional
zones, showing 16 LED zones in the D7030X/D7032 combination
Tab. 2.6:
Controla and Annunciators for the Option bus
Modules
Each FPA‑1000 supports up to two Octal Relay Modules or Octal Driver Modules.
The outputs are fully programmable and can be activated by system events. These outputs
have the same programming options as the local relays. Each output operates independently
of the other seven to provide complete flexibility. Communication with the D7035/B or D7048/
B is supervised.
Type Number
Description
D7048/B
Octal Driver Module
D7035/B
Octal Relay Module
Tab. 2.7:
Option bus modules
NAC Power Supply
The FPP‑RNAC‑8A‑4C Power supply (RNAC 8A 24V) adds four additional NACs (NFPA 72,
Class A or Class B) to the fire panel or serves as a power supply for fire protective signaling
systems. This regulated power supply provides up to 8 A of power that is used to recharge