Analog fire panels
Installing | en
75
Bosch Security Systems, Inc.
Installation and Operation Guide
2017.11 | 2.0 | F.01U.173.607
1 Positive (+) battery terminal
connection to panel
2 Interconnect cable connecting the
batteries in series
3 Negative (-) battery terminal connection to panel
Using a remote enclosure
Mount a BATB-40 or BATB-80 Battery Boxes on the left side of the FPA-1000.
For information on mounting the Battery box, see the
BATB‑40/BATB‑80 Installation
Instructions.
Connect the wires running from the batteries to the FPA-1000 battery terminals
(see the following figure):
Figure 4.25: Connecting backup batteries from a remote enclosure
Power supply (secondary) with battery backup
Battery capacity
in cabinet
in remote battery box
7.0 Ah minimum, 40 Ah maximum
7 Ah or 18 Ah
24 Ah or 38 Ah
Battery charge current
2.0 A maximum
Battery maintenance
Perform a battery load test (Pass/Fail) at least
twice per year. Replace batteries that fail the
test. Battery voltage should be ≥26 V.
Current consumption