LED Operation
Piezo
Operation
1)
System Status
2)
Supervisor
y
Yellow
On
Periodic beep
(0.5 s on, 3.5 s
off)
When the system registers a supervisory condition
Off
Silent
When no supervisory condition is registered
Silenced
Yellow
On
Silent
When an alarm or trouble condition is silenced manually by the user, or
if the system auto-silence timer expires
Off
Silent
When no condition is silenced, or when the silenced condition is
corrected
Trouble
Yellow
On
Periodic beep
(0.5 s on, 9.5 s
off)
When the panel is initializing, or when the panel registers a trouble
condition from a point or the panel, or when inputs or outputs or other
elements are bypassed
Flashing
Silent
When the panel is not operating, or when a walk test is in progress
Off
Silent
When no trouble condition exists, or when the panel is resetting
1)
Short beep upon every key press.
2)
When the panel is in the normal state (no alarm, supervisory or trouble condition), the display message is
"System Normal" along with the current date and time. If PAS or Pre-signal is turned on, the screen indicates
“SYSTEM NORMAL DAY”.
3)
Any off-normal conditions appear in groups classified as fire alarm, gas alarm, supervisory and trouble. Use the
arrow keys to view events or conditions in the same group. Up and down keys move the user to the previous or
next event, while left and right keys switch to other groups. The individual message display includes information
about the point and the specific event or condition. The initial highest priority event always appears on top.