Analog fire panels
Installing | en
71
Bosch Security Systems, Inc.
Installation and Operation Guide
2017.11 | 2.0 | F.01U.173.607
4.13
Ethernet Connection
Ethernet connection is power-limited. Monitoring the Ethernet is programmable.
For a general system connection of the fire panel to a host PC, see the following figure.
Figure 4.21: Ethernet connection
1 Fire panel
2 Ethernet/Internet
3 ITS-D6686-UL Receiver Ethernet
adapter
4 D6600 Central station receiver,
32‑line
5 Host PC running a web browser
1-2-3 Ethernet network to the
ITS‑D6686‑UL connection
3-4 ITS-D6686-UL to D6600 COM4 port
connection
2-5 Ethernet network to host PC Ethernet
network interface card (NIC)
connection
4.14
Power Supply Wiring
The FPA‑1000 allows for charging up to 40 Ah of batteries with the provided transformer
working with 120 V AC or 240 V AC.
For installations requiring battery capacity higher than 40 Ah, a regulated and UL 1481 Listed
external power supply can be used. The external power supplies connect through the panel's
battery terminals and are supervised for AC and battery fault by an Input Module (for example
FLM‑325‑2I4) on the SLC.
4.14.1
AC Power Connection
Notice!
NFPA 72 requires that the AC connection is made from a mechanically protected dedicated
branch circuit. The circuit must be marked in red and identified as a “FIRE ALARM CIRCUIT”.
The location of the circuit and its disconnecting means must be permanently noted at the fire
alarm control panel. The circuit breaker must be rated at 20 A maximum.