66
en | Installing
Analog fire panels
2017.11 | 2.0 | F.01U.173.607
Installation and Operation Guide
Bosch Security Systems, Inc.
1 FPE‑1000‑NW wired card (Port 2 Wire
out) to FPE‑1000‑NW wired card (Port
1 Wire in) connection
2 FPE‑1000‑NW wired card (Port 3
Ethernet) to FPE-1000-NE Ethernet
card (Port 1 Ethernet in) connection
3 FPE-1000-NE Ethernet card (Port 2
Ethernet out) to FPE-1000-NF Fiber
Optic card (Port 1 Ethernet)
connection
4 FPE-1000-NF Fiber Optic card (Port 3
Fiber out) to FPE-1000-NF Fiber Optic
card (Port 2 Fiber in) connection
5 FPE-1000-NF Fiber Optic card (Port 1 Ethernet) to FPE-1000-NW Wired card (Port 3
Ethernet) connection
Note: If any one connection (for example, connection 5) between two panels is removed, the
existing Class X circuit becomes a Class B circuit.
Additional notes regarding Class X:
1.
No T-taps allowed on Class X network wiring.
2.
The return side of the loop must be routed separately from the outgoing loop.
3.
The return side must not share the same conduit or cable as the outgoing side of the
loop.
4.
Refer to NFPA 72 for additional requirements of Class X circuits.
Network ground-fault detection
!
Warning!
Ground fault!
The network cards have built-in ground fault detection. The ground fault detection is located
at Port 1 on all three cards. It is also on Port 3 on the FPE‑1000‑NW card. For proper
detection, ground fault detection must be connected at only one end of each connection.
For more detailed information, see
Ground Fault Detection, page 23
.
4.8
Control Panel Terminal Connections
Danger!
Explosion and burn hazard. Do not short terminals.
Incorrect connections can result in damage to the unit and personal injury.
Before servicing this equipment, remove all power including AC, battery and phone lines.
For maximum circuit wiring distance, see module sections for the specific circuit type.
Wiring Road Map
For locations of areas of non-power-limited (A, red) and power-limited (B, green) wiring, see
the following figure.
The enclosure provides three knockouts: two at the top for power-limited and non-power-
limited connections, and one on the right side for non-power-limited connections.