162
en | User Configuration
Control Panel
2017.03 | 09 | F.01U.303.998
Program Entry Guide
Bosch Security Systems, Inc.
This function allows the user to test controlled points in areas within the keypad's scope
without sending reports to the central station.
24 hour points cannot be tested using this walk test mode.
RPS Menu Location
User Configuration > Authority Levels > Walk Test (non-fire burg points)
9.4.13
Walk Test All Fire Points
Default:
Authority Levels 1, 2, 15: Enabled (E)
Authority Levels 3-14: Blank (-)
Selections:
–
Blank (-): This function is not authorized for the user who is assigned this authority level.
–
Enabled (E): This function is authorized for the user who is assigned this authority level.
This parameter allows the user with this authority level to initiate a Fire walk test for all 24
hour points in the area to which this keypad is assigned.
When a Walk Test All Fire Points is initiated one person can typically test a fire system without
assistance. The following features are provided with the Fire Test Mode:
–
During this test, the control panel is being powered by the battery only. A battery test is
initiated during the full duration of the test to ensure the battery capacity is capable of
supporting the full load of the control panel while AC is failed.
–
This test includes a two-second bell test (fire bell output) for each fire point that is
tested.
–
The test ends once all points are tested or until the test times out in 20 minutes of no
activity.
–
Local alarm annunciation without reporting to the central station receiver.
–
Automatic smoke detector reset [SENSORS RESETTING] for all fire points programmed
with Resettable, page 199 as YES.
–
The keypad displays a sequential count after each point is activated and restored as well
as the text for the point.
–
FIRE WALK START and FIRE WALK END are reported at the central station receiver for the
beginning and end of the test.
Fire Time, page 99 for fire points programmed with Alarm Verify, page 199 as Yes is ignored
during the Fire walk test.
Authority Level 15 is reserved for the Service Passcode (User 0). You cannot change any
settings in the Authority Level 15 column.
24-Hour points left off-normal when exiting the Fire Test are bypassed. A trouble tone sounds
until it is silenced. The keypads will alternate text with the Bypass indications.
RPS Menu Location
User Configuration > Authority Levels > Walk Test All Fire Points
9.4.14
Walk Test All Invisible Burg Points
Default:
Authority Levels 1, 15: Enabled (E)
Authority Levels 2-14: Blank (-)
Selections:
–
Blank (-): This function is not authorized for the user who is assigned this authority level.
–
Enabled (E): This function is authorized for the user who is assigned this authority level.