Control Panel
Points | en
199
Bosch Security Systems, Inc.
Program Entry Guide
2017.03 | 09 | F.01U.303.998
10.3.26
Alarm Verify
Default
:
–
Point Index 5: Yes
–
All other Point Indexes: No
Selections
:
–
Yes Enable alarm verification on this point.
–
No Disable alarm verification on this point.
Use this parameter only with fire points to designate them for alarm verification.
When an alarm verification point goes into alarm, the control panel removes power to all
resettable points for the duration programmed in Restart Time. If the point (or another
resettable point in the area) is still in alarm, or goes back into alarm within 65 seconds after
the initial verification time reset, an alarm is generated.
Alarm verification points must be programmed as Resettable.
During a Fire Walk Test, the reset time is 5 seconds. The time programmed in Restart Time is
ignored.
RPS Menu Location
Points > Point Indexes > Alarm Verify
Additional resources
Restart Time, page 94
Resettable, page 199
10.3.27
Resettable
Default
:
Point Profiles 1-3, 6-63: No
Point Profiles 4,5: Yes
Selections
:
–
Yes This point is reset by the RESET SENSORS? function and during the alarm
verification sequence.
–
No This point is not resettable.
Use this parameter if this is a powered point that requires interruption of power to reset a
latched alarm event. The resettable point function is typically used with smoke detectors and
glass break detectors.
When a sensor reset is initiated, the control panel does not accept alarms from any points in
which this parameter is set to Yes. During the five-second reset time, alarms from these points
are ignored. When initiated either through a walk test or the keypad function RESET
SENSOR?, or by RPS, power is interrupted to the device for 5 seconds. SENSOR RESET is
reported to the central station receiver.
Do not mix fire and intrusion devices on the same powered loop.
RPS Menu Location
Points > Point Indexes > Resettable
10.3.28
Alarm Abort
Default
:
–
Point Profiles 1, 7-16, 20-21, 23-30: Yes
–
Point Profiles 2-6, 17-19, 22, 31 (31-63 for B9512G): No
Selections
:
–
Yes If the point goes into alarm, the system delays the alarm report for the amount of
time specified in Abort Window.
–
No If the point goes into alarm, the system immediately sends the alarm report.