en | Access
Control Panel
2017.03 | 09 | F.01U.303.998
Program Entry Guide
Bosch Security Systems, Inc.
Yes
: Fire or Gas alarm activates the output and shunts the door point.
No
: Door remains in its current mode upon a Fire or Gas alarm.
Use this parameter to activate the output for the door strike and shunt the door point upon a
Fire or Gas alarm. This feature overrides a Secure Door state, Locked Door state, Auto Door,
and an Interlock faulted point. The output activates for all doors when a Fire or Gas alarm
occurs in any area.
Notice!
This unlocks the door regardless of the armed state.
Notice!
You can return doors activated by Fire Unlock to a normal state by pressing 8 – Main menu >
3 – Actions > 8 – Access, or through the keypad with Command 46 – Access menu.
Notice!
For door controllers configured for dual authentication, Fire Unlock is only available if you
configure the associated keypad with a Passcode Enter Function of Cycle Door. All other
Passcode Enter functions use the token reader for authentication and prevent all door
functions including Fire Unlock.
RPS Menu Location
Access > Doors > Fire Unlock
12.1.12
Disarm on Open
Default
: No
Selections
:
Yes: the area only disarms after access has been granted to a user with disarm authority, and
the door point has been faulted (door was opened).
No: the area disarms when a user with a valid disarm level presents a valid token/card,
whether or not the door has been opened.
Use this program item to determine whether the door needs to be physically opened prior to
disarming the area upon a valid access request. The user initiating the access request must
have access levels that allow disarming with ID.
RPS Menu Location
Access > Doors > Disarm on Open
12.1.13
Strike Time
Default
: 10
Selections
: 1 - 240 seconds
The strike activates for the amount of time programmed.
Enter the amount of time the output for the strike activates to allow a user to open the door.
The strike activates upon a valid credential (card), Request to Enter (RTE), Request to Exit
(REX), and the keypad [CYCLE DOOR?] function.
RPS Menu Location
Access > Doors > Strike Time
12.1.14
Shunt Time
Default
: 10