220
en | Schedules
Control Panel
2017.03 | 09 | F.01U.303.998
Program Entry Guide
Bosch Security Systems, Inc.
11.5.2
All On Instant
This function simulates the All On Instant keypad function. Entries in the Parameter 1: Area #
field define the area(s) this Sked arms. The Sked can arm multiple areas. If any point is faulted
when the Sked executes, it is force armed regardless of FA/Bypass max.
11.5.3
Part On Delay
This function simulates the Part On Delay keypad function. Selections in the Parameter 1: Area
# prompt define the area(s) this Sked arms. The Sked can arm multiple areas. If any point is
faulted when the Sked executes, it is force armed regardless of FA/Bypass max.
11.5.4
Part On Instant
This function simulates the Part On Instant keypad function. Selections in the Parameter 1:
Area # prompt define the area(s) this Sked arms. The Sked can arm multiple areas. If any point
is faulted when the Sked executes, it is force armed regardless of FA/Bypass max.
11.5.5
Disarm
This function emulates the Disarm keypad function. Selections in the Parameter 1: Area #
prompt define the area(s) this Sked disarms. The Sked can disarm multiple areas.
11.5.6
Extend Close
This function sets the closing window start time to the current time plus the number of
minutes configured in Parameter 2. This function can only take effect after the Close Early
Begin time has passed.
Notice!
Extend Close time cannot extend past midnight. Furthermore, if enabled, it cannot extend
past an area's configured Latest Close Time.
11.5.7
Bypass a Point
This function emulates the Bypass Point keypad function. The entry in the Parameter 1: Point
# prompt defines the point this Sked bypasses. The point can be bypassed only if Bypassable
is programmed YES in the Point Index assigned to the point. The bypass is reported if Bypass
Reports are enabled in the Point Index assigned to the point. The Sked can bypass one point.
11.5.8
Unbypass a Point
This function emulates the Unbypass Point shortcut keypad function. The entry in the
Parameter 1: Point # prompt defines the point this function unbypasses. This function can only
bypass one point.
11.5.9
Unbypass All Points
This function is not available as a shortcut keypad function. The areas selected in the
Parameter 1: Area # prompt define the areas where this function unbypasses all points.
11.5.10
Reset Sensors
This function emulates the keypad shortcut Reset Sensors. When activated, this function
activates the area-wide-output Reset Sensors for 5 seconds. This function de-activates the
alarm output for areas selected in Parameter 1 for five seconds.
11.5.11
Turn Output On
This function emulates the Change Output State keypad shortcut to turn outputs on.