Control Panel
SDI2 modules | en
245
Bosch Security Systems, Inc.
Program Entry Guide
2017.03 | 09 | F.01U.303.998
User ports
1024-49151
Dynamic or private ports
49152-65535
Notice!
Limit unwanted traffic, choose a port number greater than 1023
In order reduce the risk of unwanted network traffic interfering with control panel IP
communications, select a port number above 1023.
RPS Menu Location
SDI2 Modules > IP Communicator > TCP/UDP Port Number
14.4.18
TCP Keep Alive Time
Default
: 45
Selections
: 0 - 65 (seconds)
This parameter sets the time in seconds between TCP keep-alive transmissions to verify that
an idle connection is still active.
The parameter has no effect on B450 Plug-in Communicator Interface operation.
RPS Menu Location
SDI2 > B42x IP Communicator > TCP keep alive time
14.4.19
IPv4 Test Address
Default
: 8.8.8.8
Selections
: IPv4 address or Domain Name
The default test address works for most networks.
The control panel uses the IP communicator to ping the IPv4 Test Address to verify the
integrity of the network and the network configuration settings.
RPS Menu Location
SDI2 > B42x IP Communicator > IPv4 Test Address
14.4.20
IPv6 Test Address
Default
: 2001:4860:4860::8888
Selections
: IPv6 address or Domain Name
The default test address works for most networks.
This parameter is only available when IPv6 Mode is set to Yes.
The control panel uses the IP communicator to ping the IPv4 Test Address to verify the
integrity of the network and the network configuration settings.
Further information
IP Address and Domain Name formats, page 282
RPS Menu Location
SDI2 > B42x IP Communicator > IPv6 test address
14.4.21
Web and Automation Security
Default
: Enable
Selections
:
–
Disable - enhanced security is not applied.
–
Enable - enhanced security is applied.
Set this parameter to Enable for enhanced security for Automation and B42x Web Access.
When enabled, HTTPS is applied to B42x Web Access changing the default value of the
HTTP Port Number, page 243 parameter. This setting also enables TLS Security for Automation.