05
Follower
06
Interior Follower
07
24-Hour
08
Key-Switch Toggle
09
Key Switch on/off
10
24 Hour Panic
11
24 Hour Fire
12
24 Hour Fire With Verification
13
Tamper
14
Bolt Contact
15
External Fault
16
Delay Exit
17
Interior Delay Exit
18
Technical Alarm
19
Reset
20
Instant Without Reset
21
Reserved
0
If a zone is not used, program the zone type location to 0. An EOL resistor is not required if
this zone type is not used. This zone type never activates the sirens or the dialer.
1 - Instant
The instant zone will perform as below:
1.
Disarm:
–
Zone normal - no Alarm / no report
–
Zone triggered - no Alarm / no report
2.
AWAY Arm:
–
Zone normal - no Alarm / no report
–
Zone triggered - Alarm / report
–
(Zone triggered during exit time no Alarm / no report)
–
(Zone triggered during entry time Alarm / report is delayed for 30sec or entry time is
expired, when system is disarmed before, no report)
3.
STAY Arm:
–
Zone normal - no Alarm / no report
–
Zone triggered - Alarm / report
–
(Zone triggered during exit time no Alarm / no report)
–
(Zone triggered during entry time Alarm / report is delayed for 30sec or entry time is
expired, when system is disarmed before, no report) When Zone is triggered, not
bypassed and system is forced to arm, a Zone fault report is sent.
–
When System is disarmed and zone is not restored before, a Zone fault restore
report is sent.
48
en | Settings
AMAX panel 4000 / AMAX panel 4000
EN
2013.07 | 03 | F.01U.267.112
Installation Guide